D286
Ionization smoke detector head
 
D603
Fixed‑temperature (135°F [57°C])
and Rate‑of‑Rise heat detector head
 
D604
Fixed‑temperature (135°F [57°C])
heat detector head
 
D605
Fixed‑temperature (190°F [88°C])
heat detector head
Modules
D275
End‑of‑line (EOL) supervision
module
Remote
Annunciators
DRA-5
Remote annunciator
Mounting Considerations
Depending on local regulations, the bases can be
surface mounted using anchors, mollies, or wing nuts.
The bases can be directly mounted on single‑gang
switch boxes or mounted on four‑inch octagonal
electrical boxes using the supplied adaptor plate.
Notice
Ensure the volume of any electrical box used
accommodates the number and size of conductors
as specified by the National Electrical Code (NEC)
or any local regulations having jurisdiction.
EOL Supervision
Use one D293E Base for the last detector on the loop
or one D275 module per detector loop. Use the EOL
resistor(s) specified by the control panel
manufacturer.
Parts included
Quant.
Component
1
D293A, D293E, or D293S Four‑wire Detector Base
1
Adaptor plate (P/N: 18851)
1
Hardware pack
1
Literature pack
Technical specifications
Electrical (D293A)
Current (alarm):
12 VDC: 58 mA; 
24 VDC: 62 mA; 
30 VDC: 75 mA maximum
Current (standby):
0.12 mA maximum
Voltage (standby):
10 VDC to 30 VDC
Electrical (D293E)
Current (alarm):
12 VDC: 82 mA; 
24 VDC: 86 mA; 
30 VDC: 100 mA maximum
Current (standby):
24 mA at 12 VDC and 24 VDC
Voltage (standby):
10 VDC to 30 VDC
Electrical (D293S)
Alarm Current
(base):
12 VDC: 48 mA; 
24 VDC: 51 mA; 
30 VDC: 70 mA maximum
Alarm
Current(sounder):
12 VDC: 15 mA; 
24 VDC: 24 mA; 
30 VDC: 25 mA maximum
Voltage (base):
10 VDC to 30 VDC
Voltage (sounder):
12 VDC nominal, 10 VDC to 16 VDC; 
24 VDC nominal, 18 VDC to 30 VDC
Environmental
Temperature
(operating):
+32°F to +100°F (0°C to +38°C)
Mechanical
Dimensions
(diameter):
6.375 in. (16.2 cm)
Outputs (D293A)
Alarm:
One normally-open (NO) relay
Auxiliary:
One set of Form C contacts rated for 62.5 VA,
0.5 A at 125 VAC and 30 W, 1.0 A at 30 VDC for
resistive loads
Outputs (D293E)
Alarm:
One normally‑open (NO) relay
Auxiliary:
One set of normally‑open (NO) contacts rated
for 62.5 VA, 0.5 A at 125 VAC and 30 W, 1.0 A
at 30 VDC for resistive loads
EOL:
One EOL relay rated for 10 W, 0.5 A at 100 VDC
for resistive loads
Outputs (D293S)
Auxiliary:
One set of normally‑open (NO) contacts rated
for 10 W, 0.5 A at 60 VDC for resistive loads
Sounder
Powered by external source
Ordering information
D293A Four‑wire Detector Base with Auxiliary Relay
(Form C)
Four‑wire detector base with an auxiliary Form C relay.
Order number 
D293A
2 | D293 Four‑wire Detector Bases