Hitachi RAC-25WPA RAC25WPA ユーザーズマニュアル

製品コード
RAC25WPA
ページ / 706
 
1-26
 
 
1.3.4 
DRY CONTACT APPLICATION (USING JUMPER WIRE) 
Applicable models: RAK-18/25/35PSA 
 
The dry contact system enables the operation of the air conditioner indoor unit to be controlled by using external dry contacts 
(with non voltage) such as card-key controller or window for facilities such as hotels. 
 
Reference  (Main PWB) 
Optional Connecting cord Accessory  
SPX-WDC3 
 
 
 
 
Connect the connecting cord to 
Main PWB CN6 (test terminal) 
 
 
 
 
Note: 
1) Dry contact function will be selected when jumper wire JP1 is “disconnected”. 
2) Select whether to disconnect or not to disconnect jumper wire JP2. 
i) Do not disconnect jumper wire JP2 if the type of Dry Contact switch to be used (for the CARD KEY UNIT or Window) is of 
contact type a (Normally Open Type). 
ii) Disconnect jumper wire JP2 if the type of Dry Contact switch to be used (for the CARD KEY UNIT or Window) is of contact 
type b (Normally Close Type). 
 
Jumper wire. 
Function 
Connection setting 
JP1 
Dry Contact function 
Not disconnect 
Disable 
Disconnect 
Enable 
JP2 
Type of Contact to be used 
Not disconnect 
Contact type a 
Disconnect 
Contact type b 
 
 
Example of wiring connection to Card Key Unit will be as below (reference only) 
CARD KEY UNIT (Prepared by INSTALLER) 
AIR CONDITIONER INDOOR PCB 
 
 
AC 
POWER 
SUPPLY 
① Connecting Cord to PCB: 
SPX-WDC3  
② Contact with sleeve 
CN6  
Jumper wire 
Dry contact 
Card sensor 
indicator 
Main PWB side 
(CN6 terminal) 
Dry Contact side 
(no polarity) 
Connecting cord 
SPX-WDC3