Opening on ceiling and suspension bolt 
 
 
 
• 
Need a connecting work for refrigerant pipe, drain 
pipe and F cable in the ceiling after suspending the 
indoor unit. Arrange drain pipe, refrigerant pipe 
and F cable in their installation position. 
• 
For finishing of opening on ceiling, arrange with 
builder in detail. 
• 
If ceiling is already completed, connecting cables 
between indoor and outdoor, piping and drain 
piping must be done before fitting the indoor unit 
Preparation for installing the indoor unit 
Installation of suspension bolts 
• 
Be sure to reinforce furring of ceiling (frame: ceiling 
joints and supporter) to maintain level of ceiling and 
prevent vibration of ceiling plate. 
• 
Suspension bolts should be purchased in the field. 
• 
Refer to the diagrams shown below for length of 
suspension bolts. 
 
In case of wooden frame 
 
In case of steel frame 
 
Wall Penetration and Installation of Protection Pipe 
• 
Drill a 
ǿ65mm hole on wall watch which is slightly 
titled towards the outdoor side. Drill the wall at a 
small angle. 
• 
Cut the protection pipe according to the wall 
thickness. 
• 
Empty gap in the sleeve of protection pipe should 
be completely sealed with putty to avoid dripping of 
rain water into the room 
Air inlet 
1000mm 
or more 
1000mm 
or more 
Air 
outlet 
Air 
outlet 
300m
m
 o
mor
Air inlet 
Air 
outlet 
1000mm 
or more 
1000mm 
or more 
Air 
outlet 
2500m
m
 
o
r less
 
650 (Panel) 
600 (Opening on ceiling 
580 (Indoor unit) 
400 (Suspension bolt) 
64 
42
 
393 (
E
lec
-box
61
0 (
S
us
pe
ns
ion b
olt
58
0 (
Indoor
 u
nit
 
60
0 (
Ope
ning 
on c
eilin
g
 
650 (
P
an
el
A
b
o
ve 300
 
110
 
285
 
32
 
Panel (optional part RAI-ECPP) 
Ceiling 
Air inlet 
Air outlet 
Air outlet 
Wide pipe φ12.7 
97(Drain) 
Drain outlet 
Narrow pipe φ6.35 
60~90mm square piece of lumber 
Suspension 
bolt (M10) 
Nut 
Angle 
Angle 
Nut 
Ceiling 
Bend slip-
preventive metal 
110
 
150~160mm 
Suspension bolt (M10) 
C type 
metal 
Concrete 
Long nut 
Suspension 
bolt (M10) 
Hanger bolt 
Angle 
Suspension 
bolt (M10) 
Ceiling 
Suspension 
bolt (M10) 
H-beam 
A
bo
ut 7
110
 
Insert 980~1470N 
(100~150kgf) 
65 
42 
55
 
112
 
62
 
230(
Dr
ai
n
227(
E
lec
-box
Reinforcing 
bar 
A
bo
ut 7