Hitachi RAC-25WPA RAC25WPA ユーザーズマニュアル

製品コード
RAC25WPA
ページ / 706
 
14-8
 
 
14.1.11 MONO SPLIT RAD-50/60/70PPA / RAC-50/60/70DPA  
Warning 
Remember that voltage of 155-170V is applied to the 0V line 
on the P.W.B. or the like as shown in the diagram below 
 
Warning 
When using an oscilloscope, never ground it. Don’t forget that 
high voltage as noted in the left figure may apply to the 
oscilloscope. 
 
 
 
 
 
 
Other Cautions 
1)  Cautions concerning for short circuit in 
servicing. 
a)  Use due caution to prevent short circuit in 
servicing. Short circuit wll immediately 
open the ICP. 
b)  If the ICP is open, remove the causes and 
replace the ICP. If the remedy is improper, 
the ICP maybe blown again. 
 
 
 
2)  The CN3 (power supply) and CN10 (fan motor) 
are the connectors with lock mechanism. Press 
the lock with your fingers to unlock and remove 
the connector. 
 
3)  When checking the voltage and waveform, do 
not connect the probes to the forbidden areas 
shown below. Touching them may cause the 
ICP1 blowout and Q11 failure. 
The Q11 is a MOS-FET and its gate terminal is 
high impedance. When a probe such as 
multimeter is contacted with gate Ⓖ, the Q11 
may have continuous ON state to supply 
overcurrent in the circuit causing the ICP1 blow 
out and Q111 failure. 
When checking the switching waveform of 
Q111, set the source Ⓢ to the base and 
measure the gate Ⓖ and drain Ⓓ. 
 
4)  During power feeding to the P.W.B., do not remove and insert the CN10 (fan motor connector). Failure to do so may cause 
overcurrent to the fan motor and P.W.B.s (microcomputer, IC and the like) and a failure may occur. To remove or insert the 
CN10, be sure to shut off the power. 
ICP2 
ICP1 
12V Power 
Circuit 
20V 
Zener diode 
ZD121 
5V 
Power 
Circuit 
12V line 
5V line 
35Vlne 
Indoor unit fan motor 
Press here 
Unlock 
Lock 
35V line 
ICP1 
0V 
Q111 
OK 
OK 
S  D 
S: Source 
D: Drain 
G: Gate 
Forbidden area (Gate to 0V) 
IC111 
0V 
Main P.W.B. 
Power source 
System Power module 2 
Indoor units 
Control 
P.W.B. 
Compressor 

DC35V 
0V 
(0V) 
ⓑ 
ⓐ 
ACT
 
m
o
d
u
le
 
P
o
w
e
r m
o
d
u
le
 
Across - (0V line)          approx 260~360V 
Across 
-ground                approx 155~170V 
Across 
 (0V line)-ground approx 155~170V 
Outdoor unit 
P.W.B. 
 
Always keep your 
hands and metallic 
things away from 
the oscilloscope 
DANGER! 
Don’t install 
the ground 
line