14.3  PRELIMINARY CHECK ON INDOOR/OUTDOOR UNIT ELECTRICAL PARTS AND 
REFRIGERATING 
 
Yes
No
No
Is the indoor unit “timer lamp” blinking?
Run the unit using the following remote 
controller settings:
In the cooling season, set the 
temperature to 16ºC in the coolng
mode.
In the heating season, set the 
temperature to 32ºC in the heating 
mode.
Does the operation lamp light or blink?
Is the compressor running?
Open  the outdoor unit and 
observe the self-diagnosis lamp 
(LD301). Count how many times 
the lamp blinks
Not running
Running
Blinks 
other than 
1 time
Troubleshoot according to the 
self-diagnosis lighting mode
Open the indoor unit and check the 
voltage between 
and 
on the 
indoor unit control P.W.B.
Normal: DC35V (32~38V)
Is the voltage correct
Check if the connecting cable 
connected incorrectly? 
inserted incompletely or 
disconnected?
Can the unit operate using the 
outdoor unit service switch? 
(See the nameplate on the 
outdoor unit ofr operating 
instructions.
Check the refrigerating cycle
In the event of overload limit cut 
or OH thermistor temperature 
resie, use the self-diagnosis 
memory function because such 
failure may evade detection due 
to ambient temperature 
variations or other factors
Check the outdoor 
electrical parts
Check the indoor 
electrical parts
No
Yes
Yes
Blinks 1 time
No
Yes