Hitachi RAC-25WPA RAC25WPA ユーザーズマニュアル

製品コード
RAC25WPA
ページ / 706
 
14-15 
 
14.4.1.2  MONOZONE / MULTIZONE / MONO SPLIT 
No
Check the indoor/outdoor 
unit connection cable, and 
conduct any defective 
section (wrong 
connection, incomplete 
insertion)
Yes
Check the outdoor unit 
power circuit, and repair 
any defective part.
No
Check according to the 
proper method for 
checking the power circuit
Is the control voltage being 
generated normally?
12V line: 12V or 7V
5V line: 5V
Yes
Check the wireless light 
receiving unit.
Do the deflectors perform initial 
operation when the power 
supply is turned ON after OFF?
Yes
No
No
Replace the 
microcomputer and 
oscillator.
Is the microcomputer clock 
signal 10Mhz at pins 
⑩ and 
being generated normally?
No
Check the reset circuit and 
repair any defective part.
Is the microcomputer reset 
input pin
n⑦ “Hi”?
Yes
Replace the control PWB
No
Check the AC outlet and 
breaker, and repair any 
defective part.
No
Is DC35V or 20V being 
generated  between terminals C 
and D on the indoor unit 
terminal board?
Is AC220~240V being 
generated between 
terminals A and B on the 
outdoor unit terminal 
board
Is DC35V being generated 
between terminals C and D 
on the outdoor unit 
terminal board?
Yes
Yes
Connect the cables 
correctly
Are C and D connection 
cables reversed?
No
Perform final operation check
Yes
Yes
 
※1: When not in operation, the unit will enter into a low power standby state, possibly causing a voltage 
drop to the 12V and 35V lines as shown 
25V~20V 
12V~7V