14-24
 
 
14.6  CHECKING BETWEEN GAS LEAKAGE AND COMPRESSOR FAULTY 
14.6.1  TROUBLESHOOTING PROCEDURE (NO OPERATION, NO HEATING OR NO COOLING) 
Connect U,V,W phase leads to the 
power module again and operate the 
air conditioner
Is the self diagnosis 
lamp mode as shown 
on the right?
Stop to operate and check 
the gas pressure in 
balancing mode
Gas leaks. Repair and 
seal refrigerant
The compressor is defective. Replace it and 
seal refrigerant.
If the compressor checker for an inverter type 
air conditioner is available, re-check using it)
Yes
• Check the system 
power module
Normal 
(4~10kg/cm
2
G)
(0.39~0.98 MPaG)
Gas leaking 
(less than 4kg/cm
2
G) 
(less than 0.39MPaG)
When the self diagnosis 
lamp lights in the same 
condition as above
Perform final check operation
Compressor
Approx 10 
secs.
Blinks
8 times
Gas 
leakage
Compressor
Possible 
faulty part
Within
30 secs
Approx. 10 secs
Time until the
lamp lights
LD301
Blinks
6 times
Blinks
5 times
Blinks
4 times
Blinks
3 times
Blinks
2 times
Self diagnosis 
lamp