14.7.6  MONO SPLIT INDOOR (RAD-50/60/70PPA) 
No 
Blinking of TIMER lamp 
Reason for indication 
Possible causes 
 
  
When the indoor heat exchanger 
temperature is too low in the heating mode 
or it is too high in the cooling mode. 
Refrigerant cycle abnormal 
1)  Reversing valve defective 
2)  Heat exchanger thermistor 
disconnected (only in heating mode) 
The malfunction mode is displayed only 
after  the abnormal condition occurs 3
rd
 time 
(read every 3 minutes 
•  Four-way valve faulty. 
*Note (for RAI & RAD) 
•  Disconnection in heat exchange 
thermistor (only during heating) 
 
 
When the outdoor unit is in forced 
operation or balancing operation after 
forced operation 
Outdoor unit forced operation. 
Electrical parts in the outdoor unit. 
 
When the interface signal from the outdoor 
unit is interrupted. 
Indoor/outdoor interface defective 
1)  Indoor interface circuit. 
2)  Outdoor interface circuit 
 
 
When the error mode is detected times 
within 30 minutes from outdoor unit 
electrical components. (However, when 
error is detected 8 times within two hours 
only for outdoor thermistor 
Outdoor electrical assembly defective 
Outdoor unit electrical components. (For 
details, operate again using remote 
controller and check from self-diagnosis 
display of outdoor unit) 
 
All stop when the float switch has been 
activated 
Abnormal water level detection 
1)  Drain stopped up 
2)  Drain pump 
3)  Float switch 
 
 
When the knob of drain pump test switch 
at indoor P.W.B main slide to “test” 
position. 
Drain pump forced operation 
Indoor PWB (Main) 
 
 
When room thermistor or heat exchanger 
thermistor is opened circuit or short circuit. 
Room thermistor or heat exchanger 
thermistor is faulty 
1)  Room thermistor 
2)  Heat exhanger thermistor 
10 
 
 
Overcurrent in indoor DC fan motor has 
been detected. 
Over-current detection at the DC fan motor  1)  Indoor fan locked 
2)  Indoor fan  motor 
3)  Indoor control P.W.B. 
11   
 
When data read from IC401 or IC402 is 
incorrect. 
IC401 or IC402 data reading error 
IC401 or IC402 abnormal 
*Note: Refer to Chapter 9 for error codes displayed on remote controllers. 
(
 Lights for 0.35 sec. at interval of 0.35 sec.) 
<Cautions> 
1)  If the interface circuit is faulty when power is supplied, the self diagnosis display will not be displayed 
2)  If the indoor unit does not operate at all, check if the connecting cable is connected to the outdoor unit. 
3)  To check operation again when the timer lamp is blinking, you can use the remote control for eoperation (except for mode 
mark ※1) 
 
1 time 
2sec 
2sec 
2 times 
2sec 
3 times 
2sec 
4 times 
2sec 
6 times 
2sec 
7 times 
2sec 
9 times 
2sec  10 times 
2sec  13 times 
※1