Hitachi RAM-53NP3A RAM53NP3A ユーザーズマニュアル
製品コード
RAM53NP3A
GENERAL DATA
2-29
2.2.19. DUCT TYPE (RAD-50PPA/60PPA/70PPA)
INDOOR
Unit
RAD-50PPA
RAD-60PPA
RAD-70PPA
Nominal capacity adjustable
-
-
-
Nominal Cooling capacity (min - max)
kW
5.0 (0.9-6.0)
6.0 (0.9-7.0)
7.1 (0.9-8.0)
Cooling sensible capacity
kW
4.0
4.5
5.1
Nominal Heating capacity (min - max)
kW
6.0 (0.9-7.0)
7.3 (0.9-8.0)
8.0 (0.9-9.0)
Noise level cooling (sound pressure)
(SL / L / M / H)
(SL / L / M / H)
dB(A)
28/30/32/34
28/30/32/34
28/30/32/35
Noise level heating (sound pressure)
(SL / L / M / H)
(SL / L / M / H)
dB(A)
29/31/33/35
29/31/33/35
29/31/33/36
Noise level (sound power)
dB(A)
60
60
61
Air flow cooling mode (SL / L / M / H)
m
3
/h
618/660/780/900
618/660/780/900
618/660/780/960
Air flow heating mode (SL / L / M / H)
m
3
/h
618/660/780/900
618/660/780/900
618/660/780/960
Fan Motor
W
56
56
56
Drain pump pressure lift
cm
-
-
-
Static pressure (SL / L / M / H)
(nominal conditions SP 00)
(nominal conditions SP 00)
Pa
-/30/50/80
-/30/50/80
-/30/50/80
Dehumidification
l/h
2.8
2.8
5.2
Included drain pump
yes
yes
yes
Max. height available for drain pump
(RAD/RAI only)
(RAD/RAI only)
500
500
500
Dimensions (H x W x D)
mm
270x900x720
270x900x720
270x900x720
Panel dimensions (H x W x D)
mm
-
-
-
Weight
kg
35.0
35.0
35.0
Colour (Munsell Code)
-
-
-
Condensate Drain
mm
φ16
φ16
φ16
Panel weight
kg
-
-
-
Panel reference
-
-
-
Color of the panel (RAL)
-
-
-
Running current
A
6.4~5.9/7.3~6.7
8.55~7.90/9.75~9.0
11.6~10.7 / 10.7~9.8
Power supply
35V DC & 230V , 1Ph ,
50Hz from outdoor unit
50Hz from outdoor unit
35V DC & 230V , 1Ph ,
50Hz from outdoor unit
50Hz from outdoor unit
35V DC & 230V , 1Ph ,
50Hz from outdoor unit
50Hz from outdoor unit
Cable section
mm²
N/A
N/A
N/A
Piping diameter (Liq / Gas)
1/4" / 1/2"
1/4" / 1/2"
1/4" / 5/8"
Drain diameter (ext)
mm
φ16
φ16
φ16
Remote control (optional only) *
SPX-RCDA/SPX-RCKA SPX-RCDA/SPX-RCKA
SPX-RCDA/SPX-RCKA
Filter
ACL Filter
-
-
-
Dimensions (H x W x D)
mm
-
-
-
Pre-filter (Standard / Optional)
Washable/-
Washable/-
Washable/-
*
more information regarding remote control can be found in Chapter 9
*
NOTE:
1. The nominal cooling and heating capacity is the
combined capacity of the HITACHI standard split
system, and are based on the ISO 5151.
system, and are based on the ISO 5151.
2. The Sound Pressure Level is based on the following
conditions:
-
1.5 meter beneath the Unit
The above data was measured in an anechoic
chamber. Please take into consideration reflected
sound of your specific site
chamber. Please take into consideration reflected
sound of your specific site
Operation Conditions
Cooling
Heating
Indoor Air Inlet Temperature
dB
27.0 °C
20.0 °C
WB
19.0 °C
Outdoor Air Inlet
Temperature
Temperature
dB
35.0 °C
7.0 °C
WB
6.0 °C
Piping Length: 5.0 meters; Piping Lift: 0 meter
dB: Dry Bulb; WB: Wet Bulb
dB: Dry Bulb; WB: Wet Bulb