FSP/Fortron CU-1110TL ユーザーズマニュアル
UPS Type
Battery Box
100%
75%
CU-1110RL
Rack 10.0 kVA
CU-1110TL
Tower 10.0 kVA
+ 1xBB-240/9RT (20 x 9Ah Batteries)
Backup Time
3
6
+ 2xBB-240/9RT (40 x 9Ah Batteries)
Backup Time
13
28
+ 1xBB-240/27T (60 x 9Ah Batteries)
Backup Time
33
43
+ 20 x 17Ah Batteries
Backup Time
9
16
+ 20 x 26Ah Batteries
Backup Time
20
29
+ 20 x 40Ah Batteries
Backup Time
38
56
+ 20 x 65Ah Batteries
Backup Time
70
104
+ 20 x 100Ah Batteries
Backup Time
104
144
P
Model
kVA
Form
Datasheet
Brochure
Manual
SNMP Card
Price Info
1
CU-1106-RL
6.0 kVA
Rack
PDF
PDF
PDF
Go to SNMP
Pricelist
2
CU-1106-TL
6.0 kVA
Tower
3
CU-1110-RL
10.0 kVA
Rack
4
CU-1110-TL
10.0 kVA
Tower
Specification
Model
CU-1106RL/TL
CU-1110RL/TL
Phase
Single Phase with ground
Capacity
6.0 kVA / 5.4 kW
10.0 kVA / 9.0 kW
Input
Voltage Range
176-300 VAC at 100% load
110-300 VAC at 75% load
Frequency Range
46Hz - 54Hz or 56Hz - 64Hz
Power Factor
≧ 0.99 @ Nominal Voltage (100% Load)
Output
Output Voltage
200/208/220/230/240 VAC
Voltage Regulation
± 1%
Frequency range
(Synchronized Range)
(Synchronized Range)
46Hz - 54Hz or 56Hz - 64Hz
Frequency Range
(Batt. Mode)
(Batt. Mode)
50Hz ± 0.1Hz or 60Hz ± 0.1Hz
Current Crest Ratio
3:1 (max.)
Harmonic Distortion
≦ 2% THD (Linear Load) ; ≦ 8% THD (Non-linear Load)
Transfer
Time
Time
Line mode to Bat. mode
Zero
Bat. mode to Line mode
Zero
Bypass to Inverter
Zero
Inverter to Bypass
Zero
Waveform (Batt. Mode)
Pure Sinewave
Efficiency
AC Line Mode
90%
Battery Mode
88%
ECO Mode
96%
Battery
Long-Run
Model
Model
Battery Type /
Numbers
Numbers
Battery Pack Voltage: 240 V
Nukbers depending on the capacity of external batteries
Charging Current
(max.)
(max.)
4.0 A
Charging Voltage
273 VDC
Indicators
LCD Display
UPS Status, Load Level, Battery level, Input/Output Voltage, Dischrage Timer and Fault conditions
Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continously sounding
AC Input & Output Connectors
AC Input Connector
Terminal
Terminal
AC Output Connector
Terminal
Terminal
Standards
IEC 62040-1 (Safety)
YES
IEC 62040-2 (EMC)
YES
CE
YES
Physical dimensions
Long-Run
Model
Model
Dimension (mm)
580 (D) x 438 (W) x 133 (H) (3U)
6680 (D) x 438 (W) x 133 (H) (3U)
Net Weight (kgs)
17
20
Environment
Humidity
0-95% RH @ 0-40°C (non-condensing)
Noise Level
Less than 58dBa @ 1 Meter