GENERAL DATA 
2-8
 
 
2.1.7.  MONOZONE OUTDOOR (RAC-25NPA/35NPA/50NPA) 
OUTDOOR 
 UNIT 
RAC-25NPA 
RAC-35NPA 
RAC-50NPA 
Minimum / Maximum indoor 
 units connectable 
  
Minimum / Maximum connected 
 capacity 
  
2.5kW 
3.5kW 
5.0kW 
Nominal Cooling capacity  
(min - max) 
kW   
REFER TO INDOOR 
REFER TO INDOOR 
REFER TO INDOOR 
Nominal Heating capacity  
(min - max) 
kW   
REFER TO INDOOR 
REFER TO INDOOR 
REFER TO INDOOR 
Nominal cooling power input  
(min - max) 
kW   
RAI -0.695 (0.155-1.050) 
RAD - 0.695 (0.155-1.050) 
RAI - 1.100 (0.155-1.280) 
RAD - 1.240 (0.155-1.280) 
RAI - 1.990 (0.155-2.200) 
RAD - 2.000 (0.155-2.060) 
Nominal heating power input 
 (min - max) 
kW   
RAI -0. 940 (0.155-1.400) 
RAD - 0.970 (0.115-1.400) 
RAI - 1.360 (0.115-1.920) 
RAD - 1.700 (0.115-1.920) 
RAI - 2.160 (0.155-2.700) 
RAD - 2.300 (0.115-2.530) 
EER / COP 
   
RAI - 3.60 / 3.72 
RAD -3.60 / 3.61 
RAI - 3.18 / 3.53 
RAD -2.82 / 2.82 
RAI - 2.51 / 2.87 
RAD -2.50 / 2.61 
SEER / SCOP 
 
RAI 
– 5.7 / 3.8 
RAD - 5.1 / 3.8 
RAI 
– 5.8 / 3.8 
RAD - 5.1 / 3.8 
RAI 
– 5.2 / 3.8 
RAD - 4.7 / 3.8 
Energy class (SEER/SCOP)   
   
RAI 
– A+ / A 
RAD - A / A 
RAI 
– A+ / A 
RAD - A / A 
RAI - A / A 
RAD - B / A 
Noise level cooling  
(sound pressure)   
 dB(A)   
46 
47 
50 
Noise level heating  
(sound pressure)   
 dB(A)   
46 
49 
52 
Noise level (sound power) 
 dB(A)   
65 
65 
65 
Air flow (Cooling / Heating)   
 m3/h   
1620/1620 
1620/1620 
2160/2160 
Static pressure  
(nominal conditions, maximum) 
Pa 
Dimensions (H x W x D) 
mm 
570x750x280 
570x750x280 
650x850x298 
Weight 
 kg   
38.0 
38.0 
45.0 
Colour (Munsell Code) 
 
 
 
 
Power supply 
   
AC  220-240V/1ph/50Hz 
AC  220-240V/1ph/50Hz 
AC  220-240V/1ph/50Hz 
Recommended fuse size 
16 
16 
16 
Starting current 
3.2/4.3 
3.2/4.3 
9.9 
Running current 
  A   
RAI: 3.20-2.93 / 4.30-3.96 
RAD: 3.19-2.93 / 4.45-4.08 
RAI: 5.05-4.63 / 6.24-5.72 
RAD: 5.69-5.22 / 7.81-7.15 
RAI: 9.1-8.37 / 9.87
–9.05  
RAD: 9.1-8.37 / 9.87-9.05  
Cable section  
 mm2   
Interconnection between indoor 
 unit and outdoor unit 
 mm2   
Piping diameter (Liq / Gas) 
  
1/4" / 3/8" 
1/4" / 3/8" 
1/4" / 1/2" 
Minimum piping length 
5.0 
5.0 
5.0 
Maximum piping  
length / height difference 
 m   
20 / 10 
20 / 10 
20 / 10 
Current quantity of refrigerant / 
Chargeless  
 kg 
1.15 
1.15 
1.40 
Chargeless / Additional 
refrigerant charge 
m / g/m 
20/- 
20/- 
20/- 
Working range (cooling / 
heating) 
 °C   
-10 ~ 43 / -15 ~ 21 
-10 ~ 43 / -15 ~ 21 
-10 ~ 43 / -15 ~ 21 
Refrigerant 
   
R410A 
R410A 
R410A 
Condenser Fan 
 
Propeller Fan 
Compressor 
Type 
   
2 Cylinder Rotary 
2 Cylinder Rotary 
2 Cylinder Rotary 
Oil Type 
 
HAF68D1/
68HES-H 
HAF68D1/
68HES-H
 
HAF68D1/
68HES-H
 
Oil Charge 
ml 
380 
380 
480 
Coil 
Resistance 
 
1.05 at 20
1.05 at 20
1.05 at 20
1.28 at 75
1.28 at 75
1.28 at 75
Quantity 
 
 
NOTE: 
1.  The nominal cooling and heating capacity is the combined capacity of 
the HITACHI standard split system, and are based on the ISO 5151. 
 
2.  The Sound Pressure Level is based on the 
following conditions:  
1.4  meter from Discharge grille 
The above data was measured in an 
anechoic chamber. Please take into 
consideration reflected sound of your 
specific site 
 
Operation Conditions 
Cooling 
Heating 
 
Indoor Air Inlet Temperature
 
dB 
27.0 °C
 
20.0 °C 
 
WB 
19.0 °C
 
 
 
Outdoor Air Inlet Temperature
 
dB 
35.0 °C
 
7.0 °C
 
 
WB 
 
6.0 °C 
 
Piping Length: 5.0 meters; Piping Lift: 0 meter 