Table 1 - Parameter list
 
SHORT 
RD/WR 
Device address 
0..255 
(*1)
 1
 
SHORT 
RD/WR 
kbps 
Baud rate (0=300, 1=600, 2=1200, 
0..7 
5
 
 
 
 
 
3= 2400, 4=4800, 5=9600. 6=19200,    
 
 
 
 
 
    7=38400 
Baud
 
SHORT 
RD/WR 
 
Only for internal use
 
 
10 
FLOAT 
RD/WR 
Current transformer I1, primary 
0..1000000 
(*2)
 5
 
12 
FLOAT 
RD/WR 
Current transformer I1, sec. 
1..5 
5
 
14 
FLOAT 
RD/WR 
Voltage transformer V1, prim. 
0..1000000 
(*2)
 400
 
16 
FLOAT 
RD/WR 
Voltage transformer V1, sec. 
100, 400 
400
 
18 
FLOAT 
RD/WR 
Current transformer I2, primary 
0..1000000 
(*2)
 5
 
20 
FLOAT 
RD/WR 
Current transformer I2, sec. 
1..5 
5
 
22 
FLOAT 
RD/WR 
Voltage transformer V2, prim 
0..1000000 
400
Adress 
Format 
RD/WR 
Unit 
Note 
Adjustment Range  Default
Parameter and Modbus address list
The following excerpt from the parameter list contains 
settings that are necessary for proper operation of the 
UMG 96RM, such as current transformers and device 
addresses. The values in the parameter list can be 
written and read.
In the excerpt, the measured value list files the measured 
and calculated measured values, output status data 
and recorded values so that they can be read.
 
(*1) 
The values 0 and 248 to 255 are reserved and must not be used.
 
(*2) 
The adjustable value 0 does not produce any sensible energy values and must not be used.