Basic functions quick guide
Adjusting the current transformer
Switch to the programming mode:
•  Press button 1 and 2 simultaneously for around 1 se-
cond to switch to the programming mode. The sym-
bols for the programming mode PRG and the current 
transformer mode CT appear on the display. 
•  Press button 1 to confirm the selection. 
•  The first digit of the input field for the primary current 
is flashing.
Adjusting the primary current
•  Press button 2 to change the flashing digit. 
•  Press button 1 to select the next digit to be chan-
ged. The selected digit to be changed is flashing. 
If the entire number is flashing, press button 2 to move 
the decimal point.
Adjusting the secondary current
•  Only 1A or 5A can be set as secondary current. 
•  Press button 1 to select the secondary current.
•  Press button 2 to change the flashing digit. 
Exit programming mode
•  Press button 1 and 2 simultaneously for around 1 se-
cond to switch to the display mode.
View measured values
Switch to the display mode:
•  If you are still in the programming mode (PRG and 
CT icons displayed on the screen), press button 1 
and 2 simultaneously for around 1 second to switch 
to the display mode.
•  A measured value display (e.g. voltage) appears 
Current transformer symbol
(in the programming mode 
only)
Adjusting current transformer, 
primary current
Display
Programming mode
Adjusting current transfor-
mer, secondary current
Button controls
•  Press button 2 to change 
the measured value dis-
play for current, voltage, 
power, etc.
•  Press button 1 to change 
the mean values, max. va-
lues etc. associated with 
the measured value.