Eaton Comet EXtreme Rack UPS, 6 kVA, standard module 67895 プリント

製品コード
67895
ページ / 2
Technical characteristics
Single-phase UPS - 
Comet EXtreme
Headquarters
140, avenue Jean-Kuntzmann
ZIRST - Montbonnot Saint-Martin
38334 Saint-Ismier Cedex - France
Tel.: +33 (0)4 76 18 30 00
CEXTR323UK
Associated communication
Solution-Pac software suite
supplied on CD with each unit
To control the protected servers (clean
shutdown) and for local or remote
supervision of the UPS.
Management-Pac 2 software suite
on CD
NMS integration kit: HP Openview, 
IBM Tivoli Netview, CA Unicenter, etc. 
SNMP/Web network card
To connect the UPS to the Ethernet
10/100 network, to relay SNMP
warnings and to supervise the UPS 
via a single Web interface.
Environment Sensor 
for the SNMP/Web card
SNMP and Web monitoring of Temperature
& Humidity & the status of 2 contacts.
JBus/ModBus card
To connect the UPS to a building
management system. 
Status information card
To relay the status of the UPS in the form
of free potential contacts plus emergency
stop.
Remote LCD display for controlling
the UPS
To remotely locate the interface of the UPS
up to 25 m and to display its parameters.
MGE PowerServices™
1-year warranty, including batteries.
Standard exchange of the product,
including the battery module, 
if it proves to be defective.
Associated services
(1)
Warranty+: peace of mind for your UPS,
extended 3-year warranty with
standard on-site exchange with the
minimum of delay.
Start Up+: guarantee of on-site
repair of the UPS efficient, quick 
and compliant with specifications.
Warranty+ Silver: includes Warranty+
and Start Up+.
Warranty+ Gold: guarantee of
continuity of service for the UPS,
includes Warranty+, Start Up+ 
and 3 site visits.
Teleservice / e-Teleservice: secure
remote monitoring of the UPS via 
the telephone network / Internet.
Commercial models
Rear view of the Comet EXtreme 6
ON/OFF
Battery operation
Operation in ON-LINE mode
Operation in manual bypass mode
Test of the indicator lamps
or shutdown of the buzzer
Overload
Alarms
Electronic fault
Battery fault
Ambient temperature > 40°C
Press and hold to display the % 
of power used
% battery capacity
RS232 communication port
Battery circuit-breaker
EXB battery extension
connector module
2 communication slots
Connector module
Input/output 
terminal block
Manual bypass
Due to developments in technical standards and the equipment described in this document, we cannot be held liable for complianc
e with the characteristics indicated by the images and text unless they are confirmed by us. All the brand names referred to in
this document are protected by copyright.
Publication: MGE UPS SYSTEMS (July 2004) - Design and rewriting: 3c-evolution.com - Integration: Pamplemousse: +33 4 79 37 87 6
6 – Translation: TTP: +33 4 78 66 47 99.
1: Depending on the country, visit
www.mgeups.com/services.
Comet EXtreme
4,5 kVA 
6 kVA 
9 kVA 
12 kVA
Performances
Power output 
3 kWatts 
3,9 kWatts 
6 kWatts 
8 kWatts 
Technology 
On-line double conversion
Input voltage
160 to 265 V at 100 % load
120 to 265 V at   65 % load
85 to 265 V at   50 % load
Input frequency
50/60 Hz (+/- 10 %)
Efficiency
92 %
Current distortions (THDI)
< 5 %
Overload capacity
250 % 1 s ; 160 % 10 s ; 130 % 60 s
Output voltage
200/208/230/240/250 Volts
Output frequency
50/60 Hz automatic selection
Operating temperature
0°C to 40°C in continuous operation
Battery capacity at 70 % load / 100 % load (typical values after 3 discharge cycles, batteries 3 to 5 years old)
Standard endurance
20 mins/12 mins 
12 mins/9 mins 
20 mins/12 mins 
12 mins/9 mins
LA endurance
45 mins/30 mins 
35 mins/20 mins 
45 mins/30 mins 
35 mins/20 mins
X LA endurance 
(1)
70 mins/55 mins 
55 mins/40 mins 
70 mins/55 mins 
55 mins/40 mins
Connection
Input/output terminal block (optional
Flexible cable 4 to 10 mm
2
Flexible cable 10 mm
2
Comet PDU terminal strip) 
Rigid cable 4 to 16 mm
2
Rigid cable 10 to 16 mm
2
Communication
Port 
1 RS 232
Communication slots 
2 slots for transverse-format cards (HTTP.XMLWebcard, Jbus, etc.)
Standards and certifications
Performance and safety 
EN 50091-3 ; EN 50091-1 ; IEC 60 950.
EMC
EN 50091-2 ; EN 55022/B,EN 55011/B, IEC 61000-4, IEC 61000-3-2.
Certification 
TÜV, GS mark, C-Tick,CE
Dimensions (H x L x D in mm) and weights
Comet EXtreme (standard endurance)
tower format 
443 x 346 x 465 ; 62 kg 
443 x 562 x 465 ; 118 kg
rack format 
354 (8U) x 483 x 462 ; 69 kg 
575 (13 U) x 483 x 462 ; 129 kg
Comet EXtreme Power Module
tower format 
443 x 173 x 465 ; 14 kg 
443 x 216 x 465 ; 22 kg
rack format
177 (4U) x 483 x 462 ; 18 kg 
221 (5U) x 483 x 462 ; 27 kg
Comet EXB Battery Module
tower format 
443 x 173 x 465 ; 48 kg 
443 x 346 x 465 ; 96 kg
rack format 
177 (4U) x 483 x 462 ; 51 kg 
354 (8U) x 483 x 462 ; 102 kg
Comet CLA Charger Module
tower format 
443 x 173 x 465 ; 14 kg 
443 x 346 x 465 ; 28 kg
rack format 
177 (4U) x 483 x 462 ; 17 kg 
354 (8U) x 483 x 462 ; 34 kg
Comet EXtreme
4,5 kVA 
6 kVA 
9 kVA 
12 kVA
Standard endurance UPS
tower format  EMC Level A 
67 861 
67 881 
67 901 
67 921
EMC Level B + EPO 
67 865 
67 885 
67 905 
67 925
rack format
EMC Level B 
67 875 
67 895 
67 915 
67 935
EMC Level B + EPO 
67 873 + 67 991 
67 893 + 67 991 
67 913 + 67 995 
67 933 + 67 995
Comet EXB Battery Module
standard tower format / EPO 
67 970 / 67 971 
67 974 / 67 975
standard rack format / EPO 
67 990 / 67 991 
67 994 / 67 995
Comet EXtreme Power Module
tower format  EMC Level A 
67 860 
67 880 
67 900 
67 920
EMC Level B 
67 863 
67 883 
67 903 
67 923
rack format
EMC Level B 
67 873 
67 893 
67 913 
67 933
Comet CLA Charger Module
tower / rack formats
67 886 / 67 896 
67 926 / 67 936
1: Higher battery capacities available in 2 XLA - contact us.
Operation in automatic bypass
mode