Yuasa YPC22-12, 12V Ah lead acid battery YPC22/12 YPC22/12 データシート

製品コード
YPC22/12
ページ / 1
YPC22-12
Nominal voltage
12
V
20-hr rate Capacity to 10.5V at 20°C
22
Ah
10-hr rate Capacity to 10.8V at 20°C
19.4
Ah
Length
181.5 (±1)
mm
Width
77 (±1)
mm
Height
166.5 (±2)
mm
(height over terminals)
N/A
mm
Mass (typical)
6.9
kg
Female threaded terminal
M5
mm
Torque
3
Nm
Storage (in fully charged condition)
Charge
Discharge
LAYOUT
Capacity loss per month at 20°C (approx)
3
%
Standard Option
Flame retardant option (FR)
13.65 (±1%)
V
2.275 (±1%)
V/cell
Float Charge voltage temperature correction factor 
(for variations from the standard 20°C)
-3
mV/cell/°C
14.5 (±3%)
V
2.42 (±3%)
V/cell
Cyclic Charge voltage temperature correction factor 
(for variations from the standard 20°C)
-4
mV/cell/°C
Float charge current limit
No limit
A
Cyclic (or Boost) charge current limit 
5.50
A
1 second
300
A
1 minute
220
A
3RD PARTY CERTIFICATIONS
ISO 9001 - Quality Management Systems
100% DOD down to 80% capacity 
300
cycles
ISO 14001 - Environmental Management Systems
75% DOD down to 80% capacity 
500
cycles
EN 18001 - OHSAS Management Systems
50% DOD down to 80% capacity 
600
cycles
25% DOD down to 80% capacity 
1400
cycles
 
UNDERWRITERS LABORATORIES Inc.
Measured at 1 kHz
15
m
Ω
STANDARDS
Refer to the technical short form
YPC
IEC61056
IEC60895-21/22
EUROBAT Classification: Standard Commercial
3 to 5
years
ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE
Issue No.: V.5 / Issue Date: Mar 2012
Installation
Can be installed and operated in any orientation except permanently inverted
Handles
PERFORMANCE & CHARACTERISTICS
MAXIMUM DISCHARGE CURRENT
CYCLIC LIFE DATA
SAFETY 
Gas Release
VRLA Batteries release hydrogen gas which can form explosive mixtures in air. Do not place inside 
a sealed container
YUASA BATTERY SALES UK LTD.     
Unit 13, Hunts Rise                                        
South Marston Industrial Estate                  
Swindon                             
SN3 4TG                                             
UK
Recycling
YUASA's VRLA batteries must be recycled at the end of life in accordance with local and national 
laws and regulations
Batteries must not be left permanently suspended by their handles (where fitted)
CASE MATERIAL
ABS (UL.94:HB)
ABS (UL94:V0)
Vent valves
Each cell is fitted with a low pressure release valve to allow gasses to escape and then reseal.
DESIGN LIFE
CHARGE VOLTAGE
Float charge voltage at 20°C
Cyclic (or Boost) charge at 20°C
CHARGE CURRENT
SPECIFICATIONS
DIMENSIONS
TERMINAL TYPE
YPC-Series - Valve Regulated Lead Acid Battery
IMPEDANCE
OPERATING TEMPERATURE RANGE
-20°C to +60°C
-15°C to +50°C
-20°C to +60°C
STORAGE