Wago 788-314 Relay DPDT-CO 60Vdc IP20 788-314 データシート
製品コード
788-314
1
64
Sockets with Miniature Switching Relay
Relay with 1 changeover contact
and status indication
(Relay height: 15 mm)
Nominal input voltage V
and status indication
(Relay height: 15 mm)
Nominal input voltage V
N
12 V, 24 V, 48 V, 60 V, 110 V DC
Relay with 2 changeover contact
and status indication
(Relay height: 15 mm)
Nominal input voltage V
and status indication
(Relay height: 15 mm)
Nominal input voltage V
N
12 V, 24 V, 48 V, 60 V, 110 V DC
Load limit curve for 788-303 to 788-307, 788-506,
788-507 and 788-508
788-507 and 788-508
Note: Inductive loads have to be attenuated by an
appropriate protective circuit in order to protect relay
coils and contacts.
appropriate protective circuit in order to protect relay
coils and contacts.
Description
V
N
I
N
Item No.
Pack.
unit
unit
V
N
I
N
Item No.
Pack.
unit
unit
Relay sockets with pluggable miniature switching
relay, for DIN 35 rail
relay, for DIN 35 rail
12 V DC
36 mA
788-303
1
12 V DC
36 mA
788-311
1
24 V DC
19.1 mA
788-304
1
24 V DC
19.1 mA
788-312
1
48 V DC
11 mA
788-305
1
48 V DC
11 mA
788-313
1
60 V DC
10.5 mA
788-306
1
60 V DC
10.5 mA
788-314
1
110 V DC
6 mA
788-307
1
110 V DC
6 mA
788-315
1
Technical Data
Accessories see pages 74 ... 77 + 80 ... 81
Accessories see pages 74 ... 77 + 80 ... 81
Contact material
AgNi 90/10
AgNi 90/10
Input voltage range
V
N
± 10 %
V
N
± 10 %
Max. switching voltage
250 V AC
250 V AC
Max. continuous current
16 A
2 x 8 A
Max. make current (resistive) at a 10 % duty cycle
4 s 30 A (AC)
4 s 15 A (AC)
Max. Switching power (resistive)
4 kVA AC, DC see load limit curve
2 x 2 kVA AC, DC see load limit curve
Max. switching rate with / without load
6 min
-1
/ 1200 min
-1
6 min
-1
/ 1200 min
-1
Operating power
400 mW typ.
400 mW typ.
Pull-in/drop-out/bounce time typ.
7 ms / 3 ms / 3 ms
7 ms / 2 ms / 3 ms
Nominal operating mode
continious duty
continious duty
Dielectric strength contact-coil
5 kV
5 kV
Dielectric strength open contact
1 kV
1 kV
Nominal voltage acc. to VDE 0110 Part 1/4.97,
IEC 60664-1
IEC 60664-1
250 V / 4 kV / 3
250 V / 4 kV / 3
Mechanical life
30 x 10
6
switching operations
30 x 10
6
switching operations
Degree of protection
IP20
IP20
Ambient operating temperature
-25 °C ... +50 °C
-25 °C ... +50 °C
Storage temperature
-40 °C ... +70 °C
-40 °C ... +70 °C
Dimensions (mm) W x H x L
15 x 54 x 86
15 x 54 x 86
Height from upper-edge of DIN 35 rail
Height from upper-edge of DIN 35 rail
Wire connection
CAGE CLAMP
®
S
CAGE CLAMP
®
S
Cross sections
0.34 mm² ... 2.5 mm² / AWG 22 ... 12
0.34 mm² ... 2.5 mm² / AWG 22 ... 12
Stripped lengths
9 ... 10 mm / 0.37 in
9 ... 10 mm / 0.37 in
Approvals
DIN VDE 0140 part 1, DIN EN 61140; DIN VDE 0160,
EN 50178; degree of protection II; UL 508
DIN VDE 0140 part 1, DIN EN 61140; DIN VDE 0160,
EN 50178; degree of protection II; UL 508
300
200
100
50
40
30
30
20
10
0.1 0.2
0.5 1
2
5 10 20
Current (A)
resistive load
Voltage (V)