Vision Akkus VISION SOLAR-AKKU 12 V, 75 AH 6FM75TX データシート
製品コード
6FM75TX
The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte
is absorbed by separators and plates and thus immobilized. Should the battery be
accidentally overcharged producing hydrogen and oxygen, special one-way valves allow the
gases to escape thus avoiding excessive pressure build-up. Otherwise, the battery is
completely sealed and is, therefore, maintenance-free, leak proof and usable in any position.
is absorbed by separators and plates and thus immobilized. Should the battery be
accidentally overcharged producing hydrogen and oxygen, special one-way valves allow the
gases to escape thus avoiding excessive pressure build-up. Otherwise, the battery is
completely sealed and is, therefore, maintenance-free, leak proof and usable in any position.
Battery Construction
Component
Positive plate
Negative plate
Container
Cover
Safety valve
Terminal
Separator
Electrolyte
Raw material
Lead dioxide
Lead
ABS
ABS
Rubber
Pb
Fiberglass
Sulfuric acid
General Features
●
Absorbent Glass Mat (AGM) technology
for efficient gas recombination of up to
99% and freedom from electrolyte
maintenance or water adding.
for efficient gas recombination of up to
99% and freedom from electrolyte
maintenance or water adding.
●
Not restricted for air transport-complies
with IATA/ICAO Special Provision A67.
with IATA/ICAO Special Provision A67.
●
UL-recognized component.
●
Can be mounted in any orientation.
●
Computer designed lead, calcium tin alloy
grid for high power density.
grid for high power density.
●
Long service life, float or cyclic
applications.
applications.
●
Maintenance-free operation.
●
Low self discharge.
Dimensions and Weight
Length(mm / inch)
258 / 10.16
Width(mm / inch)
166 / 6.54
Height(mm / inch)
206 / 8.11
Total Height(mm / inch)
215 / 8.46
Approx. Weight(Kg / lbs)
24 / 52.9
Performance Characteristics
Nominal Voltage
12V
Number of cell
6
Design Life
10 years
Nominal Capacity 77
o
F(25
o
C)
Internal Resistance
Fully Charged battery 77
o
F(25
o
C)
5.7mOhms
Self-Discharge
3% of capacity declined per month at 20
o
C(average)
Operating Temperature Range
Discharge
-20~60
o
C
Charge
-10~60
o
C
Storage
-20~60
o
C
Max. Discharge Current 77
o
F(25
o
C)
700A(5s)
Short Circuit Current
1800A
Charge Methods: Constant Voltage Charge 77
o
F(25
o
C)
Cycle use
14.4-14.7V
Maximum charging current
22.5A
Temperature compensation
-30mV/
o
C
Standby use
13.6-13.8V
Temperature compensation
-20mV/
o
C
Discharge Constant Current (Amperes at 77
o
F25
o
C)
Discharge Constant Power (Watts at 77
o
F25
o
C)
page1 of 2
www.vision-batt.com
(Note)The above characteristics data are average values obtained within
three charge/discharge cycles not the mimimum values.
three charge/discharge cycles not the mimimum values.
End Point
Volts/cell
5min 10min 15min 30min 1h
3h
5h
10h
20h 100h
1.60V
238
178
138 82.5 47.5 20.7 13.9 7.70 3.94 0.88
1.65V
224
169
133 80.0 46.9 20.3 13.7 7.65 3.90 0.87
1.70V
211
159
127 77.3 46.1 19.9 13.5 7.60 3.85 0.86
1.75V
196
150
121 74.7 45.3 19.5 13.3 7.55 3.80 0.85
1.80V
182
141
114 72.2 44.5 19.0 13.1 7.50 3.73 0.84
End Point
Volts/cell
5min 10min 15min 30min 45min 1h
2h
3h
5h
100h
1.60V
425
317
264
150 117.4 96.0 54.1 39.7 27.2 1.76
1.65V
404
306
250
148 114.4 94.1 53.2 36.9 26.7 1.75
1.70V
383
294
237
146 113.4 92.4 52.2 36.2 26.2 1.74
1.75V
361
281
224
144 110.3 90.6 51.2 35.5 25.6 1.73
1.80V
341
270
211
141 107.3 88.9 50.3 34.8 25.1 1.72
12V 88 Ah (100 hr)
Powered for Solar Applications
100 hour rate (880mA, 9.6V)
88.0Ah
10 hour rate (7.5A, 10.8V)
75.0Ah
5 hour rate (13.1A, 10.5V)
65.5Ah
6FM75T-X