Bender RCMA420-D-2 B74043002 データシート
製品コード
B74043002
TDB404006en / Main catalogue part 4 – Residual current monitors, Residual current monitoring systems / 07.2010
41
4.2
Residual current monitor RCMA420
1 -
Supply voltage U
S
see ordering information
(6 A fuse recommended)
2 -
Connector for the external W20AB…W60AB series measuring
current transformer
3 -
Alarm relay K1: I
Δn1
(prewarning)
4 -
Alarm relay K2: alarm I
Δn2
(alarm)
5 -
Combined test and reset button "T/R"
short-time pressing (< 1.5 s) = RESET
long-time pressing (> 1.5 s) = TEST
long-time pressing (> 1.5 s) = TEST
Do not route the PE conductor through the measuring current
transformer!
transformer!
Operating and display elements
Wiring diagram
1 -
Power On LED "ON" (green); lights when supply voltage is applied
and flashes in the event of system fault alarm respectively in the
event of CT malfunction.
event of CT malfunction.
2 -
Alarm LED "AL1" (yellow), prewarning; lights when the set re-
sponse value I
Δn1
is exceeded or flashes in the event of system
fault alarm respectively in the event of CT malfunction
3 -
Alarm LED "AL2" (yellow), alarm; lights when the set response
value I
Δn2
is exceeded or flashes in the event of system fault
alarm respectively in the event of CT malfunction
4 -
Multi functional LC display
5 -
Test button "T": to call up the self test.
Arrow up button: parameter change, to move up in the menu
6 -
Reset button "R": to delete saved alarms.
Down button: parameter change, to move down in the menu
7 -
"MENU" button: to call up the menu system.
Enter button: to confirm parameter change.
Press ESC: press the button > 1.5 seconds.
Press ESC: press the button > 1.5 seconds.
1
4
5
U
S
2
1
2
3
6
7
3
4
5