Bender RCMA420-D-2 B74043002 データシート

製品コード
B74043002
ページ / 40
Operation and setting
19
5.5
Display in menu mode
5.5.1
Parameter query and setting: overview
Menu 
item
Adjustable parameter
AL
Response values query and setting:
–    Residual current I2 (I
Δn2
) (AL2)
–    Residual current I1 (I
Δn1
) (AL1) 
–    Hysteresis of the response values:  % Hys 
out
Configuration of the fault memory and the alarm relays:
–    Activate/deactivate the fault memory or assign continu-
ous mode (on/off/con)
–    Select N/O operation (n.o.) or N/C operation (n.c.) 
individually for each K1/K2
–    Specify the number of the reload cycles
–    Assign the alarm category I1 (I
Δn1
) or I2 (I
Δn2
), relay test 
or device error individually to K1/K2 (1, r1/ 2, r2).
t
Set delays:
–    Response delay t
on1
/t
on2
–    Starting delay t
–    Delay on release t
off
 (LED, relay)
SEt
Device control parameter setting:
–    Select the appropriate parameter for response values:
overcurrent mode (HI), undercurrent mode (Lo) or win-
dow mode (In).
–    Enable or disable password protection, change the pass-
word.
–    Restore factory settings.
–    Service menu SyS blocked
InF
Query hard and software version
HiS
Query the first stored alarm value
ESC
Move to the next higher menu level (back)