SECU-DATA  xxxM  and  also  SECU-DATA  xxxC  have  internal  block  termi-
nals  (type: WAGO  series  256,  ATEX  certified)  for  connection  of  the  corre-
sponding external wires.  
 
Important:  
Only  qualified  personnel  with  appropriate  training  and  authorisation  by  the 
installation manager is entitled to connect  SECU-DATA xxxx to an existing 
installation. Adhere to all applicable, local safety regulations. 
 
Hint: For SECU-DATA systems using the SECU-DATA 1500C as a receiv-
er  the  function  of  the  relay  contacts  can  be  reconfigured  from  make  con-
tacts
  to  break  contacts,  see  section  Settings-SECU-DATA  1500C  relay 
configuration
 on page 25. 
 
Attention: In  case of  connection problems  SECU-DATA  maintains the 
last valid information on the receiver output. This is valid for the cur-
rent  output  of  SECU-DATA  142X  and  also  for  the  relay  outputs  of 
SECU-DATA  1500C.  For  overfill  prevention  applications  with  SECU-
DATA  1600M/1700M it is important to ensure the turn-off of pumps in 
case  of  radio  failures.  This  can  be  achieved  by  connection  the  make 
contact  of  Re1  of  the  SECU-
DATA 1500C in series to the “RF-status” 
relay contact.