Measurement uncertainty SECU-DATA 1421M/1421C- 16-Bit: 
Typical at 25°C:   
±0.02% of measured value 
Max. (-30°C 
… 75°C):  ±0.1% of measured value 
Resolution: 
 
0.4 µA 
Measurement uncertainty SECU-DATA 1420M/1420C- 12-Bit: 
Typical at 25°C:   
±0.1% of measured value 
Max. (-30°C 
… 75°C):  ±0.3% of measured value 
Resolution: 
 
6 µA 
Rise time: 
 
< 0.5 s 
Technical specification of SECU-DATA 1500M/1500C - Relay 
For the transmission of the status of the two relay contacts no further speci-
fication is required. Rated switching capacity: 30 V / 500 mA. 
 
Technical specification of SECU-DATA 1600M - NAMUR 
Switching threshold depending on the current flow through the  
NAMUR probe:
 
Probe current 
Re1 
Re2 
Meaning 
0 … 0.4 mA 
OFF 
ON 
Probe fault, “interruption”
 
1 … 2 mA 
ON 
OFF  Filling is in progress 
2 … 6 mA 
OFF 
OFF  Tank full 
> 6 mA 
OFF 
ON 
Probe fault, 
“short”
 
Technical specification of SECU-DATA 1700M - TRbF 
Threshold for the current flow through the TRbF probe: 
Probe current 
Re1 
Re2 
Meaning 
0 … 6 mA 
OFF 
ON 
Probe fault, 
“interruption” 
6 … 40 mA 
ON 
OFF  Filling is permissible 
>42 mA 
OFF 
OFF  Filling not permissible 
>105 mA 
OFF 
ON 
Probe fault, 
“short” 
Connectors of SECU-DATA 1xxxx 
The connecting wires (round cables have to be used) are fed into the hous-
ing  via  cable  glands  (M16  x  1.5,  type  SKINTOP)  with  appropriate  strain 
relief to a terminal block (type WAGO series 256). 
The  number  of  wires  and  their  functionality  depends  on  the  SECU-DATA 
model, see the appropriate section in this document. 
Norms,  standards  applied:  ETSI  EN  300  220  (5/1999/EG  R&TTE  direc-
tive).