Novatek THREE-PHASE POWER LIMITER OM-310 OM-310 データシート

製品コード
OM-310
ページ / 28
- 12 - 
ОМ-310
                                                                                                                                                       
NOVATEK-ELECTRO
 
When 
=2, the thresholds values (kW)  are defined as follows: 
Main threshold (kW) = “Pnn” * “P1F” / “100”, where 
 “Pnn” – cumulative rated load wattage, kW; 
 “P1F” – main threshold, %. 
Additional threshold (kW) = “Pnn” * “P2F” / “100”, where 
“P2F” – additional threshold, %. 
 
At any value of rPn, the additional load energizing threshold shall be determined as: 
Energizing threshold (kW) = (“Pnn” * “P2n”) /(“100”), where 
“P2F” – additional load energizing threshold, %. 
1.2.6  Protection functions 
1.2.6.1 Protection types 
 OM-310 device provides the following types of load protection: 
 
 
- maximum phase current; 
 
 
- against line-to-earth fault (based on zero sequence current): 
 
 
- for minimum line voltage; 
 
 
- for maximum line voltage; 
 
 
- for line voltages imbalance (voltage negative sequence); 
 
 
- for phase sequence order; 
 
 
- starter unit operability control. 
 
 
 
1.2.6.2 The overcurrent protection parameters are assigned relatively to the rated load current In (“
” parame-
ter).  
1.2.6.3   Overcurrent protection 
The overcurrent protection is of three-phase type. It is engaged when at least one of the phase current values 
reach the tripping threshold. 
The protection has a time delay setting. The delay can be independent (constant), or dependent (SIT - reverse 
dependent;  VIT  or  LTI  – very reverse dependent; EIT  -  extremely reverse dependent; UIT  –  ultra reverse depen-
dent; RI –type delay) - the tripping curves are displayed in Appendix 1. 
When independent time delay protection is activated (fig. 1.4), the load relay is de-energized if one of the phas-
es current exceeds the threshold value within T period of time (parameter “


” ). 
       
 
 
 Is = “
” (tripping ratio) * In (load rated current), and T – 
protection tripping delay time 
 
Example. When 
 = 4.0,  In = 10, 

 = 10.0, the load 
relay shall open in 10 sec after one of the phase currents crosses 
40 A value. 
 
 
 
 
 
 
Figure 1.4 - Principle of protection with an independent time delay 
 
 
The operation of the dependent time delay protection (Fig. 1.5) conforms to IEC  60255-3 and BS 142 stan-
dards. 
 
 
 
In corresponds to “ind” setting (rated current of 
load); 
 T (parameter “


” – protection function time 
constant) – corresponds to the trip delay time for 10 In. 
 
To deal with very high amperage currents the 
protection has a feature with an independent time delay: