When power-on inhibiting factors are not present, the load relay closure is defined by APd  parameter value 
(
ОМ-310  device operation after power-on) At =0 the load relay will not close. To close load relay in this 
case both DOWN and UP buttons have to be pressed simultaneously. 
1)  When 
=1 the load relay will close after AR time. 
2)  When 
=2 the load relay will close in 2 sec after power-on. 
 Simultaneously with the load relay closure, green LED LOAD starts to glow.  
ОМ-310 operation with remote control permitted via RS-232/RS-485 (=1, =2) is covered in paragraph 2.4.5. 
ОМ-310 operation with remote control permitted via switch (c=1, c=2) is covered in paragraph 2.4.6. 
 
2.4.1.2. 
ОМ-310 operation after a fault-caused de-energizing 
The 
ОМ-310  device operation in such case is similar to the first start operation , but the load relay closure is not 
dependent on the 
 parameter value. 
If after a fault AR is prohibited (“
=0”), the load power-on is not possible before 
ОМ-310 de-energizing. 
parameter value is effective for all types of faults except voltage faults. 
 
, 
,

 parameters shall be 
used to prohibit AR in case of voltage  faults. 
 
2.4.1.3. 
ОМ-310 operation after de-energizing tripping caused by excceding the watt input  
ОМ-310 operation in this case is covered under par. 1.2.5. 
 
 
2.4.2 OM-310 operation before load relay closure  
After load relay closure ОМ-310 performs the following: 
     - control and limiting the active and wattles power by input load wattage (1.2.5); 
     - current overload protection (1.2.6.3); 
     - protection against line-to-earth fault (1.2.6.4); 
     - voltage protection (maximum, minimum, phase imbalance) (1.2.6.5); 
 
- starter unit operability control (1.2.6.6). 
The indicator can display either phase A current or a user-selected parameter value. The value of the user-
selected parameter can be displayed either constantly (
=0), or within 15 sec, and then phase A current (=1) 
indication is displayed again. 
 
2.4.3 Characterizing relay operation 
Functions performed by the characterizing relay are defined by 
 parameter. 
When 
 =0, the relay functions as signaling alarm relay (
 and TR LEDs are off). The relay contacts are 
closed in case of any fault specified in Table  2.7. 
When 
 =1, the relay functions as time relay (TR LED glows): the relay closes upon expiration of time set by 
” parameter, after load relay closing. 
When 
 = 2, the relay is used to control switching additional load (        LED glows) (1.2.5.3).  
When 
=3 we use relay for  exceedence  signalization  of reactive power   (LEDs 
 and TR are ) 
Functional relay is switched ON by exceedence of total reactive power across tree phases –
 (admissible 
reactive power of loading) and switched OFF if not exceedence.  
When 
=4 we use relay for exceedence signalization of reactive power  main threshold (LED is blinking) 
(p.1.2.5.4.) The  threshold value is being calculated   according  p.1.2.5.2. 
 
N o t e -  When the characterizing relay is closed, contacts 1-2 are open, and contacts 2-3 are closed. 
 
 
2.4.4 Work with RS-232/RS-485 interface under MODBUS protocol in RTU mode. 
The OM allows for data exchange with an external device via serial interface under MODBUS protocol. During 
data exchange via RS-485 or RS-232 blue LED “EXCHANGE” glows.  
2.4.4.1  Communication parameters: 
- device address: 1-247 (
parameter); 
- data transfer rate: 9600 baud, 19200 baud (
 parameter); 
- response to loss of carrier: warning and continue operation, warning and load de-energizing, continue opera-
tion without warning (
 parameter); 
- response timeout detection: 1sec –120sec ( 
 parameter); 
- transmission word format – 8 bit, no parity check, two stop bits. 
2.4.4.2 
ОМ-310 control from PC 
Communication between PC and 
ОМ-310 is effected through serial interface.  The connection schematic is 
shown in fig. 2.2. Each 
ОМ-310 has a unique communication address. PC controls each OM recognizing them by 
their address. 
OM-310 can operate within RTU mode controlled Modbus networks.