Ziehl T224071 TR 210 Electronic Temperature Monitor And Controller TR 210 T224071 データシート

製品コード
T224071
ページ / 24
 
datum / name  : 13.12.2007 Fu 
Z. Nr.: 1185 0710.4 
Page  18  of  24 
Type: TR 210   
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: info@ziehl.de 
Operation: Pr9 
Pr9 
Pr9 
Pr9 
/ 2 temperature sensors, 2 limit values MIN / MAX 
 
 
At MAX-limit the warmest sensor switches the relay, at MIN the coldest. 
 
 
Operation see program Pr2 
 
 
 
Action chart: 
ϑ
1
ϑ 
sensor
ϑ
2
Relay (r), LED
Reset
t
t
 
M
M
 = measuring time
ϑ
1 = LIMIT
ϑ
2 = LIMIT +Hys teresis
doF
t
 
M
dAL
Relay locked (rL)
 
 
Reaction time of the unit – measuring time t 
M
 
The  reaction  time  of  the  unit  depends  on  the  number  of  the  connected  sensors  and  the 
measuring  function.  If  the  temperature  is  changing  constantly,  the  measuring  time  t 
M
  is 
about 2 s. If the temperature is changing rapidly, e.g. through simulation of the temperature 
with an external potentiometer, the measuring time t 
M
 is about 4 … 6 s. In case of sensor 
error the measuring time t 
M