3.4.3.4
Configuring Ethernet connection, LOGO! to S7 devices
LOGO!Soft Comfort supports the creation and configuration of Ethernet connections
between LOGO! Base Modules and S7 compatible devices.
Double-click the connection line to configure the connection settings:
Double-click the connection line to configure the connection settings:
①
LOGO! Base Module:
The LOGO Base Module is the client by default, you can set it as the client or the server here.
The LOGO Base Module is the client by default, you can set it as the client or the server here.
②
S7 Device:
The S7 device is the server by default, you can set it as the server or the client here.
The S7 device is the server by default, you can set it as the server or the client here.
③
Data transfer table
See Tools -> Ethernet Connections (0BA7 and 0BA8 only) (Page 100) for more information
See Tools -> Ethernet Connections (0BA7 and 0BA8 only) (Page 100) for more information
about data transfer configurations.
Note
If you connect the dynamic connector with an S7 compatible device, LOGO!Soft Comfort
If you connect the dynamic connector with an S7 compatible device, LOGO!Soft Comfort
disables the server/client check boxes. The LOGO! Base Module with the dynamic connector
is always the server in this connection.