3.5 Practical example 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
171
 
3.5.4 
Solution with LOGO! 
Connecting field devices 
In addition to the LOGO! device, all you need is the pressure switch and the float switches to 
control the pump. If you are using a 3-phase AC motor, a contactor relay is required for 
switching the pump. In systems with single-phase AC pumps, you must install a contactor 
relay if the current of the AC pump exceeds the switching capacity of the output relay Q1. A 
solenoid valve can usually be controlled directly, due to its low power consumption.  
Connection diagram 
 
 
Pump 
 
Mains water inlet