Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 378
 
Reference material 
 
5.1 Constants and connectors 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
195
 
The LOGO! 0BA7 and LOGO! 0BA8 devices provide a maximum of 32 shift registers bits 
S1.1 to S4.8. 
Overview (Page 191)  
 
 
This block is not available in the UDF Editor. 
5.1.1.7 
Open connectors 
 
Interconnect the output of an unused block (for example, message texts) with this block. 
Number of the open connectors: 16 (LOGO! 0BA6) or 64 (LOGO! 0BA7 and LOGO! 0BA8).  
Overview (Page 191)  
 
 
This block is available in both FBD and UDF Editors. 
5.1.1.8 
Flags 
 
 
Flag blocks output their input signal. LOGO! 0BA7 provides 27 digital flags M1 to M27 and 
16 analog flags AM1 to AM16. LOGO! 0BA8 provides 64 digital flags M1 to M64 and 64 
analog flags AM1 to AM64.  
 
 
0BA6: 27 digital flags M1 to M27; six analog flags AM1 to AM6. 
0BA4, 0BA5: 24 digital flags M1to M24; six analog flags AM1 to AM6 
0BA3, 0BA2: eight digital flags M1 to M8 
0BA1: four digital flags M1 to M4 
0BA0: zero flag 
In your block configuration, you can assign a new number to the flag, provided this flag 
number does not already exist in your circuit program. 
The output always carries the signal of the previous program cycle. This value does not 
change within the current program cycle.