5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
280
 
Operating Instructions, 06/2014 
After you set the parameter, the analog filter calculates the average value of the samples 
and assigns this value to AQ. 
Timing diagram 
 
Description of function 
The function outputs the average value after sampling the analog input signal according to 
the set number of samples. This SFB can reduce the error of analog input signal. 
 
 
Note 
There are a maximum of eight analog filter function blocks available for use in the circuit 
program in LOGO!Soft Comfort V7.0 or V8.0. 
 
5.3.3.10 
Max/Min (0BA7 and 0BA8 only) 
 
Short description 
The Max/Min function block records the maximum or minimum value.  
 
Connection 
Description 
Input En 
The function of input En (Enable) depends on the settings of parameter Mode 
and the selection of check box "when En = 0, reset Max/Min". 
Input S1 
This input is enabled when you set Mode =2: 
A positive transition (0 to 1) at input S1 sets the output AQ to the maximum 
value. 
A negative transition (1 to 0) at input S1 sets the output AQ to the minimum 
value.