5.3 Special functions 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
285
 
5.3.3.11 
Average value (0BA7 and 0BA8 only) 
 
Short description 
The average value function samples the analog input signal during configured time period 
and outputs the average value at AQ.  
 
Connetion 
Description 
Input En 
A positive edge (0 to 1 transition) at input En (Enable) sets the output AQ to the 
average value of input Ax after the configured time. A negative edge (1 to 0 
transition) holds the output at its last calculated value. 
Input R 
A positive edge (0 to 1 transition) at input R (Reset) resets the output AQ to 0. 
Input Ax 
Input Ax is one of the following analog signals: 
• 
AI1 to AI8 
(
*
)
 
• 
AM1 to AM16 (if 0BA7), or AM1 to AM64 (if 0BA8) 
• 
NAI1 to NAI32 
• 
AQ1 and AQ2 (if 0BA7), or AQ1 to AQ8 (if 0BA8) 
• 
NAQ1 to NAQ16 
• 
The block number of a function with analog output 
Parameter 
St (Sampling time): You can set it to Seconds, Days, Hours or Minutes. 
Range of values: 
If St = Seconds: 1 to 59 
If St = Days: 1 to 365 
If St = Hours: 1 to 23 
If St = Minutes: 1 to 59 
Sn (Number of samples): 
Range of values: 
If St = Seconds: 1 to St*100 
If St = Days: 1 to 32767 
If St = Hours: 1 to 32767 
If St = Minutes and St ≤ 5 minutes: 1 to St*6000 
If St = Minutes and St ≥ 6 minutes: 1 to 32767 
Output AQ 
AQ outputs the average value over the specified time of sampling. 
* AI1 to AI8: 0 to 10 V corresponds with 0 to 1000 (internal value). 
Parameter St and Sn 
Parameter St represents the sampling time and parameter Sn represents the number of 
samples.