Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート
製品コード
6ED1057-3BA00-0AA8
Reference material
5.3 Special functions
LOGO!Soft Comfort Online Help
292
Operating Instructions, 06/2014
Additional examples
Physical
quantity
Electric
quantity of
sensor
Standardized
value
Gain
Offset
Analog value
0 V
5 V
10 V
5 V
10 V
0
500
1000
500
1000
0.01
0
0
5
10
5
10
4 mA
12 mA
20 mA
12 mA
20 mA
0
500
1000
500
1000
10
0
0
5000
10000
5000
10000
0 mA
10 mA
20 mA
10 mA
20 mA
0
500
1000
500
1000
1
50
50
550
1050
550
1050
1000 mbar
3700 mbar
5000 mbar
3700 mbar
5000 mbar
O V
6.75 V
10 V
6.75 V
10 V
0
675
1000
675
1000
4
1000
1000
3700
5000
3700
5000
-30 °C
0 °C
70 °C
0 °C
70 °C
0 mA
6 mA
20 mA
6 mA
20 mA
0
300
1000
300
1000
0.1
-30
-30
0
70
0
70
5.3.4.5
0BA0 to 0BA4
Restriction for device family 0BA4
The Gain cannot be a negative value.
Calculation with the device families 0BA0 to 0BA3
With LOGO! devices from these device families, LOGO! adds or subtracts the parameter
offset to or from the standardized value before multiplying the value with the parameter gain.
Therefore, the following formulas apply:
Analog value = (standardized value + offset) x (gain x 100)
Gain (in percent) = (max
Therefore, the following formulas apply:
Analog value = (standardized value + offset) x (gain x 100)
Gain (in percent) = (max
Sensor
- min
Sensor
) / [(max
norm
– min
norm
) x 100]
Offset = [(min
Sensor
x max
norm
) – (max
Sensor
x min
norm
)] / (max
Sensor
– min
Sensor
)
Gain (in percent) = min
Sensor
/ [(min
norm
+ offset) x 100]
Offset = [max
Sensor
/ (gain x 100)] - max
norm