Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 378
Reference material 
 
5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
292
 
Operating Instructions, 06/2014 
Additional examples 
 
Physical 
quantity 
Electric 
quantity of 
sensor 
Standardized 
value 
Gain 
Offset 
Analog value 
 
0 V 
5 V 
10 V 

500 
1000 
0.01 


10 
 
4 mA 
12 mA 
20 mA 

500 
1000 
10 

5000 
10000 
 
0 mA 
10 mA 
20 mA 

500 
1000 
50 
50 
550 
1050 
1000 mbar 
3700 mbar 
5000 mbar 
O V 
6.75 V 
10 V 

675 
1000 
1000 
1000 
3700 
5000 
-30 °C 
0 °C 
70 °C 
0 mA 
6 mA 
20 mA 

300 
1000 
0.1 
-30 
-30 

70 
5.3.4.5 
0BA0 to 0BA4 
 
Restriction for device family 0BA4 
The Gain cannot be a negative value.  
Calculation with the device families 0BA0 to 0BA3 
With LOGO! devices from these device families, LOGO! adds or subtracts the parameter 
offset to or from the standardized value before multiplying the value with the parameter gain. 
Therefore, the following formulas apply: 
Analog value = (standardized value + offset) x (gain x 100) 
Gain (in percent) = (max
Sensor
 - min
Sensor
) / [(max
norm
 – min
norm
) x 100] 
Offset = [(min
Sensor
 x max
norm
) – (max
Sensor
 x min
norm
)] / (max
Sensor
 – min
Sensor
Gain (in percent) = min
Sensor
 / [(min
norm
 + offset) x 100] 
Offset = [max
Sensor
 / (gain x 100)] - max
norm