5.4 Data log profile (0BA7 & 0BA8 only) 
 
LOGO!Soft Comfort Online Help 
340
 
Operating Instructions, 06/2014 
●  AQ 
●  AM 
For digital I/O and memory, you must log data in groups of eight bits, for example, I1 to I8, 
Q9 to Q16, M17 to M24. For analog data, you select one value to log, for example, AI1, AQ2, 
or AM1. You configure function block values in groups of eight bits or single values, 
depending on the value type (digital or non-digital). 
You can log a maximum of 32 items (analog values or eight-bit digital groups) in the data log. 
 
You can only configure the data log from LOGO!Soft Comfort. You can not create, configure, 
or delete the data log from a LOGO! device. 
5.4.3 
Transferring the data log 
After configuring the data log, you can download the circuit program into LOGO! 0BA7 or 
LOGO! 0BA8 devices which store the data log in internal EEPROM. 
You can transfer the data log to your PC or an SD card in .CSV format. To upload the data 
log from the internal EEPROM to your PC, use the menu command "Tools -> Transfer -> 
Upload Data Log (0BA7 and 0BA8 only) (Page 78)", and the LOGO! 0BA7 or LOGO! 0BA8 