5.6 Circuit programs 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
365
 
●  Retentivity off: The function occupies RAM space 
●  Retentivity on: The function occupies REM space 
Here you will find information on memory space provide by LOGO!. (Page 365)  
5.6.2.2 
Memory space 
For LOGO! 0BA7 and LOGO! 0BA8 devices, you can use up to 400 blocks in your circuit 
program. 
The maximum memory space a LOGO! circuit program can use is as follows: 
●  RAM: 8000 bytes (if 0BA7) or 8500 bytes (if 0BA8) 
●  Retentive data (REM): 250 bytes 
For LOGO! 0BA6 devices, you can use up to 200 blocks in your circuit program. 
The maximum memory space a LOGO! circuit program can use is as follows: 
●  RAM: 3800 bytes 
●  Retentive data (REM): 250 bytes 
The Info Window displays the memory space used when you select the Tools → Determine 
LOGO! (Page 90) menu command, or when you press the function key (Page 31) [F2]. 
 
 
The following specifications apply 
 
LOGO! series 
Blocks 
Par 
RAM 
Timer 
REM 
Flags 
 
LOGO! 0BA4 to 
0BA5 
130 
Not 
restricted 
Not 
restricted 
Not 
restricted 
60 
24 
 
LOGO! 0BA2 to 
0BA3 
56 
48 
27 
16 
15 
 
LOGO! 0BA1 
56 
48 
27 
16 
15 
 
LOGO! 0BA0 
30 
27 
24 
10 
0/7 
A circuit program consists of a number of blocks, which start with an input and end with an 
output. 
Nesting depth (LOGO! series 0BA0, 0BA1) 
The number of blocks in a circuit program describes the nesting depth. 
I/O in the sense of nesting depth are: 
●  Inputs (I (Page 193) , AI (Page 196)) 
●  High, Low (Hi, Lo (Page 194)) 
●  Memory markers (M (Page 195)) 
●  Outputs (Q (Page 194)) 
Blocks in the sense of nesting depth are: