Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 378
 
User interface 
 
2.8 Menu bar 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
55
 
2.8.1.13 
File -> Properties - Hardware type 
This tab shows the basic information of LOGO! Basic, such as known blocks, 
constants/connectors, and the number of digital inputs. 
2.8.1.14 
File -> Properties - I/O settings 
When you download the circuit program, LOGO!Soft Comfort also transfers the I/O settings 
to LOGO!. 
With the setting 
, you can set what the analog outputs of LOGO! should be when LOGO! 
is in STOP mode and the range of the outputs value. Your choices are as follows. 
For "Behavior of analog outputs in STOP mode", select one of the following choices: 
●  All outputs keep the last value 
●  AQ1 to AQ8 are set to values that you define 
For "Set analog outputs value range type", select one of the following choices:  
●  0 mA to 20 mA or 0 V to 10 V 
●  4 mA to 20 mA 
With the setting 
, you can choose to enable the optional AI3 and AI4 on the LOGO! 0BA6, 
0BA7 and 0BA8 devices that have an option of four analog inputs. For LOGO! 0BA6, 0BA7 
and 0BA8 devices that support four analog inputs, you can choose how many to use. Your 
choices are as follows: 
●  Enable 0 AIs: No AI available for use in your circle diagram. 
●  Enable 2 AIs: Only AI1 and AI2 corresponding to input terminals I7 and I8 are available 
for use in your circuit program. 
●  Enable 4 AIs: AI1 and AI2 corresponding to input terminals I7 and I8 are available for use 
in your circuit program. Additionally, AI3 and AI4 corresponding to input terminals I1 and 
I2 are available for use. 
LOGO! 0BA8 devices support 8 analog inputs and 24 digital inputs.