LOGO! functions 
 
4.3 Special functions 
 
LOGO! 
128
 
Manual, 06/2014, A5E33039675 
Connector X at SF inputs  
The connector "x" input for any SF input is low. That is, the input carries a "lo" signal.  
Parameter inputs  
At some of the inputs you do not apply any signals. You configure the relevant block values 
instead. Examples: 
●  Par (Parameter): 
You do no connect the Par parameter. Instead, you set the relevant blcok parameters 
(times, on/off thresholds etc.). 
●  Priority: 
This is an open input. Here, you define priorities and specify whether a message is to be 
acknowledged in RUN. 
4.3.2 
Time response 
Parameter T 
You can configure a time value T for some of the SF blocks. When you preset this time, note 
that your input values are based on the timebase set:  
 
Timebase 
_ _ : _ _ 
s (seconds) 
seconds : 
1
/
100
 seconds 
m (minutes) 
minutes : seconds 
h (hours) 
hours : minutes 
 
The LOGO! 0BA8-specific stopwatch (Page 171) function provides an additional timebase - 
10 ms.  
Accuracy of T 
Because of slight tolerances in the characteristics of electronic components, the set time T 
can deviate. You can find a detailed description of such deviations in the "On-delay" topic 
(Page 136).  
Accuracy of the timer (weekly/yearly timer) 
To prevent timing inaccuracy of the real-time clock in C versions (LOGO! devices with an 
integrated real-time clock) caused by this deviation, LOGO! continuously compares the timer