Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
148
 
Manual, 06/2014, A5E33039675 
4.4.6 
Edge-triggered wiping relay 
Short description 
An input pulse generates a preset number of output pulses with a defined pulse/pause ratio 
(retriggerable), after a configured delay time has expired.  
 
Symbol in LOGO! 
Wiring 
Description 
 
 
Input Trg 
A signal at input Trg (Trigger) triggers the times for 
the edge triggered wiping relay. 
Input R 
A signal at input R resets the current time (T
a
) and the 
output. 
Parameter 
The interpulse width T
L
 and the pulse width T
H
 are 
configurable. 
N determines the number of pulse/pause cycles 
TL/TH: 
 Range of values: 1...9 
Retentivity:  
/ = No retentivity 
R = The status is retentive. 
Output Q 
Q is set after TL expires, and reset after TH expires. 
Parameters TH and TL 
Note the information on parameter T in topic Time response (Page 128). 
The actual value of another already-programmed function can provide the pulse width TH 
and the interpulse width TL. You can use the actual values of the following functions:  
●  Analog comparator  (Page 188) (actual value Ax – Ay) 
●  Analog threshold trigger  (Page 183) (actual value Ax) 
●  Analog amplifier  (Page 195) (actual value Ax) 
●  Analog multiplexer  (Page 213) (actual value AQ) 
●  Analog ramp  (Page 216) (actual value AQ) 
●  Mathematic instruction (Page 227) (actual value AQ) 
●  PI controller  (Page 220) (actual value AQ) 
●  Up/down counter  (Page 173) (actual value Cnt) 
●  Analog filter (Page 232) (actual value AQ) 
●  Average value (Page 237) (actual value AQ) 
●  Max/Min (Page 234) (actual value AQ) 
●  On-delay  (Page 136) (current time Ta) 
●  Off-delay  (Page 140) (current time Ta) 