LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
180
 
Manual, 06/2014, A5E33039675 
4.4.17 
Threshold trigger 
Short description 
The output is set and reset with two configurable threshold triggers.  
 
Symbol in LOGO! 
Wiring 
Description 
 
Input Fre 
The function counts the 0 to 1 transitions at input Fre. 
1 to 0 transitions are not counted. 
Use the following as the input: 
• 
inputs I3, I4, I5, I6 for fast counting (only LOGO! 
12/24RCE/RCEo and LOGO! 24CE/24CEo): max. 
5 kHz, if the fast input is directly connected to the 
threshold trigger function block 
• 
any other input or circuit component for counting 
low frequency signals (typically 4 Hz) 
Parameter 
On: on threshold 
Range of values: 
0000...9999 
Off: off threshold 
Range of values: 
0000...9999 
G_T: time interval or gate time during which the input 
pulses are measured 
Range of values: 
00:00 s...99:99 s 
Output Q 
Q is set and reset at the thresholds. 
Parameter G_T 
The gate time G_T can be provided by the actual value of another already-programmed 
function. You can use the actual values of the following functions:  
●  Analog comparator  (Page 188) (actual value Ax – Ay) 
●  Analog threshold trigger  (Page 183) (actual value Ax) 
●  Analog amplifier (Page 195) (actual value Ax) 
●  Analog multiplexer (Page 213) (actual value AQ) 
●  Analog ramp (Page 216) (actual value AQ) 
●  Mathematic instruction (Page 227) (actual value AQ) 
●  PI controller (Page 220) (actual value AQ) 
●  Up/down counter (Page 173) (actual value Cnt) 
●  Analog filter (Page 232) (actual value AQ) 
●  Average value (Page 237) (actual value AQ) 
●  Max/Min (Page 234) (actual value AQ)