LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
188
 
Manual, 06/2014, A5E33039675 
4.4.20 
Analog comparator 
Short description 
The output is set and reset depending on the difference Ax - Ay and on two configurable 
thresholds.  
 
Symbol in LOGO! 
Wiring 
Description 
 
Inputs Ax and Ay 
Inputs Ax and Ay are one of the following analog 
signals:  
• 
AI1 to AI8 (*) 
• 
AM1 to AM64 
• 
NAI1 to NAI32 
• 
AQ1 to AQ8 
• 
NAQ1 to NAQ16 
• 
Block number of a function with analog output 
Parameter 
A: gain 
 Range of values: -10.00 to 10.00 
B: ero offset  
 Range of values: -10,000 to 10,000 
On: on threshold 
 Range of values: -20,000 to 20,000 
Off: off threshold 
 Range of values: -20,000 to 20,000 
p: number of decimals 
 Range of values: 0, 1, 2, 3 
Output Q 
Q is set or reset, depending on the difference Ax - Ay 
and the set thresholds.. 
* AI1...AI8: 0...10 V corresponds with 0...1000 (internal value). 
Gain and offset parameters 
For more information on the gain and offset parameters, refer to topic "Calculating the gain 
Parameters On and Off 
The actual value of another already-programmed function the on threshold On and the off 
threshold Off. You can use the actual values of the following functions: 
●  Analog threshold trigger (Page 183) (actual value Ax) 
●  Analog amplifier (Page 195) (actual value Ax) 
●  Analog multiplexer (Page 213) (actual value AQ) 
●  Analog ramp (Page 216) (actual value AQ) 
●  Mathematic instruction (Page 227) (actual value AQ)