Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
192
 
Manual, 06/2014, A5E33039675 
4.4.21 
Analog watchdog 
Short description 
This special function saves the process variable of an analog input to memory, and sets the 
output when the output variable exceeds or drops below this stored value plus a configurable 
offset.  
 
Symbol in LOGO! 
Wiring 
Description 
 
Input En 
A positive edge (0 to 1 transition) at input En saves 
the analog value at input Ax ("Aen") to memory and 
starts monitoring of the analog range Aen - Δ
 2
 to 
Aen+ Δ
 1
 
Input Ax 
Input Ax is one of the following analog signals:  
• 
AI1 to AI8 (*) 
• 
AM1 to AM64 
• 
NAI1 to NAI32 
• 
AQ1 to AQ8 
• 
NAQ1 to NAQ16 
• 
Block number of a function with analog output 
Parameter 
A: gain 
 Range of values: -10.00 to 10.00 
B: zero offset  
 Range of values: -10,000 to 10,000 
Δ
1
: difference value above Aen: 
 on/off threshold  
 Range of values: 0 to 20,000 
Δ
2
: difference value below Aen: 
 on/off threshold  
 Range of values: 0 to 20,000 
p: number of decimals 
 Range of values: 0, 1, 2, 3 
Retentivity:  
/ = no retentivity 
R = the status is retentive in memory 
Output Q 
Q is set/reset, depending on the stored analog value 
and the offset. 
* AI1...AI8: 0...10 V corresponds with 0...1000 (internal value). 
Gain and offset parameters 
For more information on gain and offset parameters, refer to topic "Calculating the gain and