Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
 
LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 06/2014, A5E33039675 
213
 
4.4.28 
Analog multiplexer 
Short description 
This special function outputs one of four predefined analog values or 0 at the analog output.  
 
Symbol in LOGO! 
Wiring 
Description 
 
Input En 
A change in status from 0 to 1 at input En (Enable) 
switches a parameterized analog value to the output 
AQ, depending on the value of S1 and S2. 
Inputs S1 and S2 
S1 and S2 (selectors) for selecting the analog value 
to be issued. 
• 
S1 = 0 and S2 = 0:  
value 1 is issued. 
• 
S1 = 0 and S2 = 1:  
value 2 is issued. 
• 
S1 = 1 and S2 = 0:  
value 3 is issued. 
• 
S1 = 1 and S2 = 1:  
value 4 is issued. 
Parameter 
V1 to V4: analog values that will be issued. 
 Range of values: -32768 to 32767 
p: number of decimals 
 Range of values: 0, 1, 2, 3 
Output AQ 
This special function has an analog output. This 
output can only be connected with analog inputs, 
analog flags, analog outputs or network analog 
outputs. 
Range of values for AQ: 
-32768 to 32767 
Parameters V1...V4 
The analog values for the parameters V1to V4 can be derived from another already-
programmed function. You can use the actual values of the following functions:  
●  Analog comparator (Page 188) (actual value Ax – Ay) 
●  Analog threshold trigger (Page 183) (actual value Ax) 
●  Analog amplifier (Page 195) (actual value Ax) 
●  Analog ramp (Page 216) (actual value AQ) 
●  Mathematic instruction (Page 227) (actual value AQ) 
●  PI controller (Page 220) (actual value AQ) 
●  Up/down counter (Page 173) (actual value Cnt) 
●  Analog multiplexer (actual value AQ) 
●  Analog filter (Page 232) (actual value AQ)