LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
220
 
Manual, 06/2014, A5E33039675 
4.4.30 
PI controller 
Short description 
Proportional-action and integral-action controllers. You can use both types of controller 
individually or combined.  
 
Symbol in LOGO! 
Wiring 
Description 
 
Input A/M 
Set the mode of the controller: 
1: automatic mode 
0: manual mode 
Input R 
Use the input R to reset the output AQ. As long as 
this input is set, the input A/M is disabled.  
Output AQ is set to 0. 
Input PV 
Analog value: process variable, influences the output 
Parameter 
SP: set-value assignment 
 Range of values:  
 -10,000 to 20,000 
KC: gain 
 Range of values:  
 00.00 to 99.99 
TI: integral time 
 Range of values:  
 00:01m to 99:59 m 
Dir: action direction of the controller  
 Range of values:  
 + or - 
Mq: value from AQ with manual mode 
 Range of values:  
 0 to 1,000 
Min: minimum value for PV 
 Range of values:  
 -10,000 to 20,000 
Max: maximum value for PV 
 Range of values:  
 -10,000 to 20,000 
A: gain 
 Range of values:  
 -10.00 to 10.00 
B: offset 
 Range of values:  
 -10,000 to 10,000 
p: number of decimals 
 Range of values: 
 0, 1, 2, 3 
Output AQ 
This special function has an analog output (= 
manipulated variable). This output can only be 
connected with analog inputs, analog flags, analog 
outputs or network analog outputs. 
Range of values for AQ: 
0 to 1,000