Configuring LOGO!
8.2 Setting the default values for LOGO!
LOGO!
266
Manual, 06/2014, A5E33039675
Setting the menu language in programming mode
You can set the menu language in programming mode only:
1. In the main menu of programming mode, move the cursor to "
1. In the main menu of programming mode, move the cursor to "
①
": Press or
2. Confirm "
①
": Press OK
3. Move the cursor to "
②
": Press or
4. Confirm "
②
": Press OK
5. Move the cursor to the language of your choice: Press or
6. Confirm language selection: Press OK
6. Confirm language selection: Press OK
8.2.4
Setting the number of AIs in LOGO!
LOGO! 12/24RCE/RCEo and LOGO! 24CE/24CEo support up to four onboard inputs that
can be used as either digital or analog inputs (0 V to 10V). Inputs I7 (AI1) and I8 (AI2) are
available as analog inputs by default, whether you use them or not. Inputs I1 (AI3) and I2
(AI4) are optional analog inputs. LOGO! provides a menu where you can choose to use two
analog inputs (the default, AI1 and AI2), or four, or even zero. Regardless of the settings,
inputs I1 and I2 can be used as digital inputs. To use them as analog inputs AI3 and AI4, you
must set the number of analog inputs to four. Note that the number of configured analog
inputs on LOGO! affects the subsequent numbering of analog inputs on attached expansion
modules (see the "Maximum setup (Page 29)" topic).
You can set the number of AIs in programming mode only.
You can set the number of AIs in programming mode only.