Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
 
Technical data 
 
A.3 Technical data: LOGO! DM8 230R and LOGO! DM16 230R 
LOGO! 
Manual, 06/2014, A5E33039675 
295
 
 
LOGO! 230RCEo 
LOGO! 230RCE 
Surge current 
Incandescent lamp load (25000 
switching cycles) at 
• 
230/240 VAC 
• 
115/120 VAC 
Max. 30 A 
 
 
• 
1000 W 
• 
500 W 
Max. 30 A 
 
 
• 
1000 W 
• 
500 W 
Fluorescent tubes with ballast 
(25000 switching cycles) 
10 x 58 W (at 230/240 VAC) 
10 x 58 W (at 230/240 VAC) 
Fluorescent tubes, conventionally 
compensated (25000 switching 
cycles) 
1 x 58 W (at 230/240 VAC) 
1 x 58 W (at 230/240 VAC) 
Fluorescent tubes, uncompensated 
(25000 switching cycles) 
10 x 58 W (at 230/240 VAC) 
10 x 58 W (at 230/240 VAC) 
Short circuit-proof cos 1  
Power protection B16, 600 A 
Power protection B16, 600 A 
Short circuit-proof cos 0.5 to 0.7 
Power protection B16, 900 A 
Power protection B16, 900 A 
Derating 
None; across the entire 
temperature range 
None; across the entire 
temperature range 
Parallel output circuits for power 
increase 
Not permitted 
Not permitted 
Protection of output relay (if 
desired) 
Max. 16 A, characteristic B16  Max. 16 A, characteristic B16 
Switching rate 
Mechanical 
10 Hz 
10 Hz 
Ohmic load/lamp load 
2 Hz 
2 Hz 
Inductive load 
0.5 Hz 
0.5 Hz 
Notice: For fluorescent lamps with capacitors, you must consider the technical data of 
fluorescent lamp ballasts. If the current exceeds the maximum allowed surge current, 
appropriate contactor relays must switch the flourescent lamps. 
The data was determined with the following devices: 
●  Siemens fluorescent tubes 58 W VVG 5LZ 583 3-1 uncompensated. 
●  Siemens fluorescent tubes 58 W VVG 5LZ 583 3-1 parallel compensated with 7 μF. 
●  Siemens fluorescent tubes 58 W VVG 5LZ 501 1-1N with ballast. 
A.3 
Technical data: LOGO! DM8 230R and LOGO! DM16 230R 
 
 
LOGO! DM8 230R 
LOGO! DM16 230R 
Power supply 
Input voltage 
115 VAC/VDC to 240 VAC/VDC  115 VAC/VDC to 240 VAC/VDC 
Permissible range 
85 VAC to 265 VAC 
100 VDC to 253 VDC  
85 VAC to 265 VAC 
100 VDC to 253 VDC  
Permissible mains frequency 
47Hz to 63 Hz