Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート
製品コード
6ED1057-3BA00-0AA8
Technical data
A.4 Technical data: LOGO! 24...
LOGO!
298
Manual, 06/2014, A5E33039675
LOGO! DM8 230R
LOGO! DM16 230R
Mechanical
10 Hz
10 Hz
Ohmic load/lamp load
2 Hz
2 Hz
Inductive load
0.5 Hz
0.5 Hz
Notice: For fluorescent lamps with capacitors, you must consider the technical data of
fluorescent lamp ballasts. If the current exceeds the maximum allowed surge current,
appropriate contactor relays must switch the flourescent lamps.
The data was determined with the following devices:
● Siemens fluorescent tubes 58 W VVG 5LZ 583 3-1 uncompensated.
● Siemens fluorescent tubes 58 W VVG 5LZ 583 3-1 parallel compensated with 7 μF.
● Siemens fluorescent tubes 58 W VVG 5LZ 501 1-1N with ballast.
The data was determined with the following devices:
● Siemens fluorescent tubes 58 W VVG 5LZ 583 3-1 uncompensated.
● Siemens fluorescent tubes 58 W VVG 5LZ 583 3-1 parallel compensated with 7 μF.
● Siemens fluorescent tubes 58 W VVG 5LZ 501 1-1N with ballast.
A.4
Technical data: LOGO! 24...
LOGO! 24CE
LOGO! 24CEo
Power supply
Input voltage
Input voltage
24 VDC
Permissible range
20.4 VDC to 28.8 VDC
Reverse polarity protection
Yes
Permissible mains frequency
- -
Power consumption from 24 VDC
15 mA to 50 mA (no load on digital output)
1.2 A (with max. load on digital output)
1.2 A (with max. load on digital output)
Voltage failure buffering
- -
Power loss at 24 VDC
0.4 W to 1.2 W
Backup of the real-time clock at 25 °C
Typ. 20 days
Accuracy of the real-time clock
Typ. ± 2 s/day
Digital inputs
Number
Number
8
Electrical isolation
No
Numbef of high speed inputs
4 (I3, I4, I5, I6)
Input frequency
•
•
Normal input
•
High speed input
•
Max. 4 Hz
•
Max. 5 kHz
Max. continuous permissible voltage
28.8 VDC
Input voltage
Signal 0
Signal 1
Signal 0
Signal 1
L+
< 5 VDC
> 12 VDC
< 5 VDC
> 12 VDC