Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
Technical data 
 
A.12 Technical data: LOGO! AM2 AQ 
 
LOGO! 
310
 
Manual, 06/2014, A5E33039675 
 
LOGO! AM2 RTD 
Reverse polarity protection 
Yes 
Ground terminal  
For connecting ground and shielding of the measuring 
line. 
Sensor inputs 
Number 
Type 
PT100 or PT1000 with the default temperature 
coefficient of α = 0.003850 for both Types, or 
compatible sensors. 
Connection of sensors 
• 
2-wire technique 
• 
3-wire technique 
 
• 
Yes 
• 
Yes 
Measurement range 
-50 °C to +200 °C 
-58 °F to +392 °F 
Settings for the measurement display on 
the LOGO! Basic: 
• 
1 °C steps 
• 
0.25 °C steps 
(rounded to one decimal) 
• 
1 °F steps 
• 
0.25 °F steps 
(rounded to one decimal) 
 
 
• 
Offset: -50, Gain: 0.25 
• 
Offset: -500, Gain: 2.50 
 
• 
Offset: -58, Gain: 0.45 
• 
Offset: -580, Gain: 4.50 
Curve linearization 
No 
Measuring current Ic 
Pulse current signal: 
PT100: 0.5 mA 
PT1000: 0.5 mA 
Measurement rate 
Depends on the installation 
Typ. 50 ms 
Resolution 
0.25 °C 
Error limits (3-wire technique) 
• 
0 °C to +200 °C 
• 
-50 °C to 200 °C 
Of the final measured value: 
• 
± 2 °C 
• 
± 2 °C 
Electrical isolation 
No 
Cable length (twisted) 
Max. 10 m 
Interference frequency suppression 
50 Hz, 60 Hz 
A.12 
Technical data: LOGO! AM2 AQ 
 
 
LOGO! AM2 AQ 
Power supply 
Input voltage 
24 VDC