Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
LOGO! without display ("LOGO! Pure") 
 
  
 
LOGO! 
322
 
Manual, 06/2014, A5E33039675 
Ethernet interface (Page 48) to find the details about the wiring of the Ethernet interface and 
also about the status of the Ethernet LEDs. 
Operating characteristics 
LOGO! is ready for operation when you switch on power. Switching off a LOGO! without 
display is equivalent to disconnecting the power supply. 
You can not start or stop the circuit program of LOGO!...o versions by means of buttons, 
therefore, this is why the LOGO!...o versions have other startup characteristics. 
Startup characteristics 
If there is no circuit program in LOGO! or on the inserted micro SD card, LOGO! remains in 
STOP mode. 
If there is a valid circuit program in LOGO! memory or on the micro SD card, LOGO! 
automatically switches from STOP mode to RUN mode when you switch on power. 
LOGO! automatically copies the circuit program on an inserted micro SD card to memory, 
immediately after you switch on power. LOGO! rewrites the existing circuit program in 
memory if one exists, and then changes from STOP mode to RUN mode. 
By connecting an Ethernet cable to LOGO! (Page 285), you can use LOGO!Soft Comfort to 
download the circuit program and place LOGO! in RUN mode. 
Operating status indication 
An LED on the front panel indicates the operating state:  
●  Lights red: Power On/STOP 
●  Lights green: Power On/RUN 
The LED lights red after Power On and in all LOGO! states other than RUN mode. The LED 
lights green when LOGO! is in RUN mode. 
Reading current data 
LOGO!Soft Comfort provides an online test for reading the current data of all functions while 
the system is in RUN. 
If your LOGO! without display holds a protected micro SD card, you cannot read the current 
data unless you enter the correct password (Page 281) for the circuit program. LOGO! 
deletes the circuit program from memory when you remove the micro SD card. 
Deleting the circuit program 
Use LOGO!Soft Comfort to delete the circuit program and password if a password exists.