Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
LOGO! installation and wiring 
 
2.3 Wiring LOGO! 
 
LOGO! 
40
 
Manual, 06/2014, A5E33039675 
Sensor characteristics for LOGO! 
 
 
LOGO! 12/24RCE 
LOGO! 12/24RCEo 
LOGO! 24CE 
LOGO! 24CEo 
LOGO! DM8 
12/24R 
LOGO! DM8 
24 
I3 ... I6 
I1,I2,I7,I8 
I3 ... I6 
I1,I2,I7,I8 
I1 ... I8 
I1 ... I8 
Signal status 0 
Input current 
< 5 VDC 
< 0.85 mA 
< 5 VDC 
< 0.05 mA 
< 5 VDC 
< 0.85 mA 
< 5 VDC 
< 0.05 mA 
< 5 VDC 
< 0.85 mA 
< 5 VDC 
< 0.85 mA 
Signal status 1 
Input current 
> 8.5 VDC 
> 1.5 mA 
> 8.5 VDC 
> 0.1 mA 
> 12 VDC 
> 2 mA 
> 12 VDC 
> 0.15 mA 
> 8.5 VDC 
> 1.5 mA 
> 12 VDC 
> 2 mA 
 
 
 
LOGO! 24RCE (AC) 
LOGO! 24RCEo (AC) 
LOGO! DM8 24R (AC) 
LOGO! 24RCE (DC) 
LOGO! 24RCEo (DC) 
LOGO! DM8 24R (DC) 
LOGO! 230RCE (AC) 
LOGO! 230RCEo (AC) 
LOGO! DM8 230R (AC) 
LOGO! 230RCE (DC) 
LOGO! 230RCEo (DC) 
LOGO! DM8 230R (DC) 
Signal status 0 
Input current 
< 5 VAC 
< 1.0 mA 
< 5 VDC 
< 1.0 mA 
< 40 VAC  
< 0.03 mA 
< 30 VDC  
< 0.03 mA 
Signal status 1 
Input current 
> 12 VAC 
> 2.5 mA 
> 12 VDC 
> 2.5 mA 
> 79 VAC 
> 0.08 mA 
> 79 VDC 
> 0.08 mA 
 
 
 
LOGO! DM16 24R 
LOGO! DM16 24 
LOGO! DM16 230R (AC)  LOGO! DM16 230R (DC) 
Signal status 0 
Input current 
< 5 VDC 
< 1.0 mA 
< 5 VDC 
< 1.0 mA 
< 40 VAC  
< 0.05 mA 
< 30 VDC  
< 0.05 mA 
Signal status 1 
Input current 
> 12 VDC 
> 2.0 mA 
> 12 VDC 
> 2.0 mA 
> 79 VAC 
> 0.08 mA 
> 79 VDC 
> 0.08 mA 
 
 
 
Note 
LOGO! 230RCE/230RCEo and expansion module DM16 230R each contains two groups of 
four inputs, for a total of eight. Within each group, you must operate all inputs on the same 
phase. Different phases are only possible between the groups. 
Example: I1 to I4 on phase L1, I5 to I8 on phase L2. 
You must not connect the inputs of the LOGO! DM8 230R to different phases. 
 
Sensor connections 
Connecting glow lamps and two-wire proximity switches (Bero) to LOGO! 230RCE/230RCEo 
or LOGO! DM8 230R (AC) and LOGO! DM16 230R (AC) 
The figure below shows how you connect a switch with a glow lamp to LOGO!. The current 
that flows through the glow lamp allows LOGO! to detect a "1" signal even though the switch 
contact is not closed. If, however you use a switch that has the glow lamp fitted with a power 
supply, this response does not occur.