2.3 Wiring LOGO! 
LOGO! 
Manual, 06/2014, A5E33039675 
45
 
LOGO! AM2 
 
  FE terminal for connecting earth and 
shielding the analog measuring cable 
  Cable shielding 
  Earth 
  Standard DIN rail 
The illustration above shows an example of four-wire current measurement and two-wire 
voltage measurement. 
Connecting a two-wire sensor to the LOGO! AM2 
Wire up the two-wire sensor's connecting wires as follows: 
1.  Connect the sensor's output to connection U (0 V to 10 V voltage measurement) or to 
connection I (0/4 mA to 20 mA current measurement) of the AM2 module. 
2.  Connect the plus connector on the sensor to the 24 V supply voltage (L+). 
3.  Connect the ground connection of the current output M (on the right side of the sensor, as 
shown in the figure above) to the corresponding M input (M1 or M2) on the AM2 module. 
LOGO! AM2 RTD 
You can connect a maximum of two PT100 sensors or two PT1000 or one PT100 plus one 
PT1000 sensor in a two-wire or three-wire connection or in a mixed use of two-wire and 
three-wire connection to the module. Note that the sensor type supported by the module is 
only PT100 or PT1000 with the default temperature coefficient of α= 0.003850. 
For a two-wire connection, you need to short-circuit terminals U1- and IC1 or U2- and IC2. 
Errors caused by the ohmic resistance of the measuring line are not compensated for this 
type of connection. If a PT100 sensor is connected, a line resistance of 1 Ω is proportional to 
measuring error of +2.5 °C; if a PT1000 sensor is connected, a line resistance of 1 Ω is 
proportional to measuring error of +0.25 °C. 
A three-wire technique suppresses the influence of the cable length (ohmic resistance) on 
the result of the measurement.