Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
LOGO! installation and wiring 
 
2.4 Putting into operation 
 
LOGO! 
52
 
Manual, 06/2014, A5E33039675 
STOP 
RUN 
Action of LOGO!: 
• 
The input data is not read. 
• 
The circuit program is not executed. 
• 
The relay contacts are permanently open 
or the solid-state outputs are switched off. 
Action of LOGO!: 
• 
LOGO! reads the status of the inputs. 
• 
LOGO! uses the circuit program to calculate the 
status of the outputs. 
• 
LOGO! switches the relay/solid-state outputs on 
or off. 
 
 
 
Note 
After switching the power on, the system briefly switches through the outputs on the LOGO! 
24CE/24CEo. With an open circuit, a voltage of > 8 V can occur for up to approximately 100 
ms; when the circuit is loaded, this time reduces to a matter of microseconds. 
 
LOGO! expansion modules, operating states 
LOGO! expansion modules have three operating states. The color of the LED (RUN/STOP) 
indicates one of three operating states for LOGO! expansion modules. 
 
Green (RUN) 
Red (STOP) 
Orange/Yellow 
The expansion module 
communicates with the device 
to the left. 
The expansion module does not 
communicate with the device to 
its left. 
Initialization phase of the 
expansion module