Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
Programming LOGO! 
 
3.7 Writing and starting the circuit program 
 
LOGO! 
84
 
Manual, 06/2014, A5E33039675 
When you select a special or basic function block, LOGO! shows you the relevant function 
block and positions the solid square cursor on the block. Press OK to enter the editing mode, 
and the cursor appears as a flashing solid square. Press   or   to select the required block. 
Select your block (off-delay, see the next figure), and then press OK: 
 
Press   to move the cursor to Trg, and then press OK. 
Press   or   to select B1 and confirm with OK. 
 
LOGO! automatically connects the uppermost input of the new block to B1, which you had 
previously connected to Q1. Note that you can only interconnect digital inputs with digital 
outputs or analog inputs with analog outputs. LOGO! otherwise removes the 'old' block. 
The off-delay block has two inputs and a parameter. At the top is the trigger input (Trg) you 
use to start the off-delay time. In our example, the OR block B1 triggers the off-delay. You 
reset the time and the output with a signal at the reset input (R). You set the off-delay time at 
parameter T of the Par. 
Assigning block parameters 
Now you set the off-delay time T: 
1.  Move the cursor to Par: Press   
2.  Switch to editing mode: Press OK 
LOGO! shows the parameters in the parameter assignment window: 
 
To change the time value, follow these steps: 
1.  Move the cursor to the time value: Press   
2.  Switch to editing mode: Press OK