Programming LOGO! 
 
3.8 Configuring additional functions for LOGO! 
 
LOGO! 
98
 
Manual, 06/2014, A5E33039675 
7.  Apply "
": Press OK 
LOGO! shows the following display: 
 
LOGO! indicates the current setting of the automatic synchronization function by the 
circle with a dot. The default setting is "
"; that is, the synchronization is disabled. 
8.  To enable synchronization, press   or   to select "
", and then confirm with OK. 
Enabling/disabling synchronization in parameter assignment mode 
If you want to enable/disable automatic synchronization in parameter assignment mode, 
select "
" in the parameter assignment menu , then menus "
" and "
". You can now 
enable/disable automatic synchronization. 
 
3.8 
Configuring additional functions for LOGO! 
After you have successfully created the second circuit program, you can configure additional 
functions by means of the following menu commands:  
●  Network 
●  Diagnostics 
UDF and Data Log 
You can configure the UDF and Data Log functions only from LOGO!Soft Comfort. After you 
have configured them in LOGO!Soft Comfort and downloaded them to the LOGO! 0BA8 
device, you can then edit elements connected to these functions from the device: 
●  UDFs (User-Defined Functions) 
●  Data Log 
Network digital and analog I/O 
You can configure the following connectors representing network digital or analog 
inputs/outputs only from LOGO!Soft Comfort: 
●  Network digital inputs 
●  Network analog inputs